Click on the vendors specific EQUIPMENT NAME to go to that Listing.

Vendor Equipment Name Leak Rate / Threshold / Max Product Surface Area
ASTTest Services, Inc. ASTTest Mass Balance Leak Detection System [(product surface area in ft² ÷ 5,575 ft²) x 0.88 gph]/[(product surface area in ft² ÷ 5,575 ft²) x 0.44 gph]/13,938 ft².
Engineering Design Group, Inc. EDG XLD 2000 Plus (Revision 1.02) Leak Detection System (MTS DDA Magnetostrictive Probe) [(product surface area in ft² ÷ 12,074 ft²) x 1.92 gph]/[(product surface area in ft² ÷ 12,074 ft²) x 0.96 gph]/12,076 ft².
Ronan X-76 CTM Automatic Tank Gauging System (MTS Level Plus UST Probe) [(product surface area in ft² ÷ 564 ft²) x 0.2 gph]/[(product surface area in ft² ÷ 564 ft²) x 0.96 gph]/846 ft².
Leak Detection Technologies MDleak Enhanced Leak Detection and Leak Location Method 0.005 gph/A tank should not be declared tight when chemical marker is detected outside of the tank/Not limited by capacity.
Mass Technology Corp. Precision Mass Measurement Systems SIM-1000 and CBU-1000 (24 hour test) [(product surface area in ft² ÷ 1,257 ft²) x 0.1 gph]/[(product surface area in ft² ÷ 1,257 ft²) x 0.05 gph]/ Not limited by product surface area.
Precision Mass Measurement Systems SIM-1000 and CBU-1000 (48 hour test) [(product surface area in ft² ÷ 6,082 ft²) x 0.294 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.147 gph]/6,082 ft².
Precision Mass Measurement Systems SIM-1000 and CBU-1000 (72 hour test) [(product surface area in ft² ÷ 14,200 ft²) x 0.638 gph]/[(product surface area in ft² ÷ 14,200 ft²) x 0.319 gph]/Not limited by product surface area.
Praxair Services, Inc.
(originally listed as Tracer Research, Corp.)
Tracer ALD 2000 Automated Tank Tightness Test 0.1 gph/ A tank system should not be declared tight when tracer chemical or hydrocarbon greater that the background level is detected outside of the tank./Not limited by capacity.
Universal Sensors and Devices, Inc. LTC-1000 (Mass Buoyancy Probe) [(product surface area in ft² ÷ 14,244 ft²) x 1.4 gph]/[(product surface area in ft² ÷ 14,244 ft²) x 0.7 gph]/35,610 ft².
LTC-2000 (Differential Pressure Probe) [(product surface area in ft² ÷ 14,244 ft²) x 3.0 gph]/[(product surface area in ft² ÷ 14,244 ft²) x 1.5 gph]/35,610 ft².
Varec, Inc. (originally listed as Coggins Systems, Inc., and later as Endress + Hauser Systems and Gauging) FuelsManager and Remote Terminal Unit RTU/8130 (MTS Magnetostrictive Probe) [(product surface area in ft² ÷ 616 ft²) x 0.2 gph]/[(product surface area in ft² ÷ 616 ft²) x 0.1 gph]/924 ft².
FuelsManager with Barton Series 3500 ATG (48 hour test) (72 hour test) [(product surface area in ft² ÷ 6,082 ft²) x 2.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 1.0 gph]/15,205 ft².
Varec, Inc. FuelsManager with MTS M-Series ATG (MTS Magnetostrictive Probe) [(product surface area in ft² ÷ 11,786 ft²) x 4.50 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 2.25 gph]/ 11,786 ft²
FuelsManager with Enraf 854 ATG (Servo Buoyancy Probe) [(product surface area in ft² ÷ 11,786 ft²) x 3.00 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 1.50 gph]/ 11,786 ft²
Vista Precision Solutions, Inc. (originally listed as Vista Research, Inc. and Naval Facilities Engineering Service Center) LRDP-24 (V1.0.2, V1.0.3) [(product surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph – 0.223 gph)]/15,205 ft².
LRDP-48 (V1.0.2, V1.0.3) [(product surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph – 0.188 gph)]/15,205 ft².
LRDP-24 (V1.1) [(product surface area in ft² ÷ 6,082 ft²) x 0.856 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.632 gph]/15,205 ft².
LRDP-48 (V1.1) [(product surface area in ft² ÷ 6,082 ft²) x 0.749 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.563 gph]/15,205 ft².