Issue Date: June 14, 2008
Varec, Inc.
FuelsManager
with Enraf 854 ATG
(Servo Buoyancy Probe)
BULK UNDERGROUND STORAGE TANK LEAK DETECTION (50,000 gallons or
greater)
Certification |
Leak
rate is proportional to product surface area (PSA).
For tanks with PSA of 11,786 ft², leak rate is 3.00 gph with PD = 95.3% and
PFA = 4.7%
For other tank sizes, leak rate equals [(PSA in ft² ÷ 11,786 ft²) x 3.00
gph].
Example:
For a tank with PSA = 10,000 ft²; leak rate = [(10,000 ft² ÷ 11,786 ft²) x
3.00 gph] = 2.54 gph.
Leak rate
may not be scaled below 0.2 gph. |
Leak Threshold |
Leak
threshold is proportional to product surface area (PSA).
For tanks with PSA of 11,786 ft², leak threshold is 1.50 gph.
For other tank sizes, leak threshold equals [(PSA in ft² ÷ 11,786 ft²) x
1.50 gph].
Example:
For a tank with PSA = 10,000 ft²; leak threshold = [(10,000 ft² ÷ 11,786
ft²) x 1.50 gph] = 1.27 gph.
A tank system should not be declared tight if the test result indicates a
loss or gain that equals or exceeds the calculated leak threshold. |
Applicability |
Gasoline, diesel, aviation fuel. |
Tank Capacity |
Use
limited to single, field-constructed, vertical-walled tanks 50,000 gallons
to 2,100,000 gallons.
Maximum product surface area (PSA) is 11,786 ft².
Tank must be at least 44% full. |
Waiting Time |
None.
Testing may be initiated immediately following a delivery provided a minimum
of 72 hours of quality data are collected and analyzed. |
Test Period |
Minimum of 72 hours.
There must be no dispensing or delivery during test. |
Temperature |
Measurement not required by this system.
System is self-compensating for product temperature changes.
Buoyancy of float changes with product density in response to temperature
changes. |
Water Sensor |
None.
Water ingress leaks are measured as an increase in product level inside the
tank. |
Calibration |
Servo
product level measurements must be verified annually and, if necessary,
calibrated in accordance with manufacturer's instructions. |
Comments |
Not
evaluated using manifolded tank systems.
Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to
lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected.
Evaluated in a nominal 2,100,000 gallon vertical underground tank with
diameter of 122.5 ft., height of 23.4 ft., and PSA of 11,786 ft².
System is a volumetric measurement test method. |
Varec, Inc. |
Evaluator:
Ken Wilcox Associates |
5834 Peachtree
Corners East |
Tel:
(816) 443-2494 |
Norcross, GA 30092 |
Date of Evaluation:
04/07/08 |
Tel: (770) 447-9202 |
|
|
|
|