| Issue Date: August 9, 2001 Revision Date: December 
21, 2005
 
Varec, Inc. (originally 
listed as Coggins Systems, Inc. and later as Endress + Hauser Systems and 
Gauging)
 FuelsManager
and Remote Terminal Unit RTU/8130 (MTS Magnetostrictive Probe)
 BULK UNDERGROUND STORAGE TANK 
LEAK DETECTION METHOD (50,000 gallons or greater) 
  
    | Certification | Leak rate is
      proportional to product surface area (PSA). For tanks with PSA of 616 ft², leak rate is 0.2 gph with PD = 96.4% and
      PFA = 3.6%
 For other tank sizes, leak rate equals [(PSA in ft² ÷ 616 ft²) x 0.2
      gph].
 Example:
 For a tank with PSA = 900 ft²; leak rate = [(900 ft² ÷ 616 ft²) x 0.2
      gph] = 0.29 gph.
 Leak rate may not be scaled below 0.2 gph.
 |  
    | Leak
      Threshold | Leak threshold is
      proportional to product surface area (PSA). For tanks with PSA of 616
      ft², leak threshold is 0.1 gph. For other tank sizes, leak threshold
      equals [(PSA in ft² ÷ 616 ft²) x 0.1 gph].
 Example:
 For a tank with PSA = 900 ft²; leak threshold = [(900 ft² ÷ 616ft²) x
      0.1 gph] = 0.1gph.
 A tank system should not be declared tight if the test result indicates a
      loss or gain that equals or exceeds the calculated leak threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuel. |  
    | Tank
      Capacity | Use limited to
      single field-constructed vertical tanks 50,000 gallons or greater. Maximum product surface area (PSA) is 924 ft².
 Product must be at full
      operating level.
 |  
    | Waiting
      Time | Minimum of 4
      hours, 26 minutes after delivery or dispensing. |  
    | Test
      Period | Minimum of 24
      hours. There must be no dispensing or delivery during test.
 |  
    | Temperature | Average for
      product is determined by a minimum of 5 resistance temperature detectors (RTDs). Product temperature change during test should not exceed 0.72 degrees F.
 |  
    | Water
      Sensor | Must be used to
      detect water ingress. Minimum detectable water level in the tank is 0.238
      inch. Minimum detectable change in water level is 0.0017 inch.
 |  
    | Calibration | Probe must be
      checked and, if necessary, calibrated in accordance with manufacturer's
      instructions. |  
    | Comments | Tests only
      portion of tank containing product. As product level is lowered, leak rate in a leaking tank decreases (due to
      lower head pressure).
 Consistent testing at low levels could allow a leak to remain
      undetected.
 FuelsManager uses PC-based software to process probe data.
 Remote Terminal Unit (RTU/8130) contains software embedded in a CPU housed
      in a stand-alone console.
 Evaluated in a nominal 50,000 gallon vertical
      underground tank with product surface area (PSA) of 616 ft².
 The maximum product level in the tank during test was 65% (32,500
      gallons).
 |    
  
    | 
      
      
      Varec, 
      Inc.
      
      
       | Evaluator: 
      Ken Wilcox Associates
      
      
       |  
    | 5834 Peachtree Corners East
      
      
       | Tel:  (816) 443-2494
      
      
       |  
    | Norcross, GA 30092
      
      
       | Date of Evaluation: 
      11/24/98
      
      
       |  
    | Tel:  (770) 447-9202
      
      
       |  
      
      
       |  |