| Issue Date:  June 14, 2008 
Varec, Inc.  
FuelsManager with 
MTS M-Series ATG(MTS Magnetostrictive Probe)
 
BULK UNDERGROUND STORAGE TANK LEAK DETECTION (50,000 gallons or 
greater) 
  
    | 
    Certification | Leak 
    rate is proportional to product surface area (PSA). For tanks with PSA of 11,786 ft², leak rate is 4.50 gph with PD = 96.3% and 
    PFA = 3.7%
 For other tank sizes, leak rate equals [(PSA in ft² ÷ 11,786 ft²) x 4.50 
    gph].
 Example:
 For a tank with PSA = 10,000 ft²; leak rate = [(10,000 ft² ÷
    11,786 ft²) x 4.50 gph] = 3.80 gph.
 Leak rate 
    may not be scaled below 0.2 gph.
 |  
    | 
    Leak Threshold | Leak 
    threshold is proportional to product surface area (PSA). For tanks with PSA of 11,786 ft², leak threshold is 2.25 gph.
 For other tank 
    sizes, leak threshold equals [(PSA in ft² ÷ 11,786 ft²) x 2.25 gph].
 Example:
 For a tank with PSA = 10,000 ft²; leak threshold = [(10,000 ft² ÷ 
    11,786 ft²) x 2.25 gph] = 1.91 gph.
 A tank system should not be declared tight if the test result indicates a 
    loss or gain that equals or exceeds the calculated leak threshold.
 |  
    | 
    Applicability | 
    Gasoline, diesel, aviation fuel.  |  
    | 
    Tank Capacity | Use 
    limited to single, field-constructed, vertical-walled tanks having a 
    capacity of 50,000 to 2,100,000 gallons. Maximum product surface area (PSA) is 11,786 ft².
 Tank must be at least 44% full.
 |  
    | 
    Waiting Time | None.Testing may be initiated immediately following a delivery provided a minimum 
    of 72 hours of quality data are collected and analyzed.
 |  
    | 
    Test Period | 
    Minimum of 72 hours. There must be no dispensing or delivery during test.
 |  
    | 
    Temperature | 
    Average for product is determined by resistance temperature detectors (RTDs) 
    located at 18 inch increments from the bottom of the tank. |  
    | 
    Water Sensor | Must 
    be used to detect water ingress. Minimum detectable water level in the tank is based on the length of the 
    probe as follows:
 <25 feet = 3.0 inches
 <40 feet = 3.8 inches
 <60 feet = 4.7 inches
 The water sensor “inactive zone” can be countered by installing the probe 
    over the tank sump.
 Minimum detectable change in water level is 0.015 inch.
 Water ingress sensing is continuous and independent of leak detection 
    testing.
 |  
    | 
    Calibration | No 
    scheduled maintenance or recalibration is required.The sensor pipe should be checked annually for build up of process material.
 Floats should move freely along the sensor pipe.  If they do not, routine 
    cleaning should be performed.
 |  
    | 
    Comments | Not 
    evaluated using manifolded tank systems.Tests only portion of tank containing product.
 As product level is lowered, leak rate in a leaking tank decreases (due to 
    lower head pressure).
 Consistent testing at low levels could allow a leak to remain undetected.
 Evaluated in a nominal 2,100,000 gallon vertical underground tank with 
    diameter of 122.5 ft., height of 23.4 ft., and PSA of 11,786 ft².
 System is a volumetric measurement test method.
 |    
  
    
      | Varec, Inc. | Evaluator: 
      Ken Wilcox Associates |  