| Issue Date: December 5, 2002 Engineering Design 
Group, Inc. Ronan X-76 CTM 
Automatic Tank Gauging System (MTS Level Plus UST Probe)
 BULK UNDERGROUND STORAGE TANK 
LEAK DETECTION METHOD (50,000 gallons or greater)
 
  
    | Certification | Leak rate is proportional to product 
    surface area (PSA). For tanks with PSA of 564 ft², leak rate is 0.2 gph with PD > 99.9% and PFA 
    < 0.1%.
 For other tank sizes, leak rate equals [(PSA in ft² ÷ 564 ft²) x 0.2 gph].
 Example: For a tank with PSA = 846 ft²; leak rate = [(846 ft² ÷ 564 ft²) x 
    0.2 gph] = 0.3 gph.
 Leak rate may not be scaled below 0.2 gph.
 |  
    | Leak Threshold | Leak threshold is proportional to product 
    surface area (PSA). For tanks with PSA of 564 ft², leak threshold is 0.1 gph.
 For other tank sizes, leak threshold equals [(PSA in ft² ÷ 564 ft²) x 0.96 
    gph].
 Example: For a tank with PSA = 846 ft²; leak threshold = [(846 ft² ÷ 564 
    ft²) x 0.1 gph] = 0.15 gph.
 Leak threshold may not be scaled below 0.1 gph.
 A tank system should not be declared tight if the test result indicates 
    a loss or gain that equals or exceeds the calculated leak threshold.
 |  
    | Applicability | Gasoline, diesel, aviation fuel, fuel oil 
    #4. |  
    | Tank Capacity | Use limited to single, field-constructed, 
    vertical-walled tanks having a capacity of 50,000 to 75,000 gallons. Maximum product surface area (PSA) is 846 ft².
 |  
    | Waiting Time | Minimum of 4 hours, 48 minutes after 
    delivery or transfer. |  
    | Test Period | Minimum of 6 hours. There must be no 
    delivery, transfer, or dispensing during test. |  
    | Temperature | Average for product is determined by five 
    resistance temperature detectors (RTDs). |  
    | Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 0.874 inch.
 Minimum detectable change in water level is 0.011 inch.
 For tanks with a product surface area (PSA) of 564 ft² and containing 0.874 
    inches of water, system takes more than 64 days to detect a 0.20 gph water 
    ingress rate.
 |  
    | Calibration | System must be checked and, if necessary, 
    calibrated in accordance with manufacturer's instructions. |  
    | Comments | Tests only portion of tank containing 
    product. As product level is lowered, leak rate in a leaking tank decreases (due to 
    lower head pressure).
 Consistent testing at low levels could allow a leak to remain undetected.
 Evaluated in nominal 50,000 gallon tank with PSA of 564 ft².
 |    
  
    | 
    Engineering Design Group, Inc. | 
    Evaluator:  Ken Wilcox Associates |  
    | 
    
    Manufacturer’s Previously Listed Contact Information is No 
    Longer Valid. | Tel:  
    (816) 443-2494 |  
    |   | Date of 
    Evaluation:  11/16/01 |  |