Issue Date: October 27,
2004
Revision Date: June 27, 2011
Western Fiberglass, Inc.
Co-Flow
Hydraulic Interstitial Monitoring System
CONTINUOUS INTERSTITIAL MONITORING METHOD (LIQUID FILLED)
Certification:
Certified as a continuous, liquid-filled
interstitial space leak detection system for use only with Western Fiberglass,
Inc., double-walled/coaxial flexible pipelines.
Maximum length is 200 feet.
No restrictions on pipeline diameter.
Operating Principle:
Similar to the methodology that has been
applied to liquid-filled interstitial double-walled tanks.
Propylene glycol is used to fill the interstice.
Two reservoirs are used to contain the liquid, one at each end of the system.
The reservoir at one end is closed to the atmosphere, includes a valve that is
used to fill the system, and is designed to operate at a lower elevation than
the other reservoir. The reservoir at the other end is open at the top and
contains a dual-point level sensor.
The dual-point level sensor system monitors the liquid level in the interstitial
reservoir and provides an alarm if the liquid level is either too high (ingress
of liquid) or too low (egress of liquid).
The method must be used with a dual-point sensor system that will properly fit
into the reservoir, is compatible with the interstitial liquid, and is on the
NWGLDE list.
Sensors can be used to shut down the turbine system and/or alert the operator
that a potential problem exists.
Alarm Conditions:
Leak Rate |
|
Time to Alarm* (hours) for 5-Inch Sensor Spacing as a
Function of Leak Rate for Various Reservoir Diameters (in) |
|
Time to Alarm* (hours) for 3-Inch Sensor Spacing as a
Function of Leak Rate for Various Reservoir Diameters (in) |
(gph) |
|
3.75 |
3 |
2.87 |
2 |
1.5 |
|
3.75 |
3 |
2.87 |
2 |
1.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
0.05 |
|
4.8 |
3.0 |
2.8 |
1.4 |
0.76 |
|
2.9 |
1.8 |
1.7 |
0.8 |
0.5 |
0.10 |
|
2.4 |
1.5 |
1.4 |
0.68 |
0.38 |
|
1.4 |
0.91 |
0.84 |
0.41 |
0.23 |
0.20 |
|
1.2 |
0.76 |
0.70 |
0.34 |
0.19 |
|
0.71 |
0.46 |
0.42 |
0.20 |
0.11 |
*Time to alarm is based on evaluations conducted with
100% glycol solution and a leak (liquid egress) 190 feet from the highest
reservoir. Leaks closer to the highest elevation reservoir, and the use of a
diluted glycol solution, will shorten alarm times. Both theoretical calculations
and laboratory measurements confirm that dilution of the propylene glycol used
in the interstice of the WFG system will produce a significant reduction in the
alarm time. This system has not been evaluated for locations with temperatures
outside the range of 32 to 100 degrees Fahrenheit.
*Time to alarm for a catastrophic primary pipe failure with a pressure of
40 psi is 20 seconds at a distance of 10 feet from the reservoir and 84 minutes
at a distance of 190 feet. This is based on a 5-inch spacing of the float
sensors.
Applicability:
Western Fiberglass,
Inc. underground double-walled/coaxial flexible pipelines containing gasoline,
gasohol, diesel, heating oil #2, kerosene, aviation fuel, or motor oil.
Calibration:
Equipment requires no calibration other than to insure the
upper reservoir is half full.
The
electronics must be calibrated and maintained in accordance with the
sensor/monitoring equipment instructions.
Comments:
Pipeline fittings with interstitial communication tubing must
only be located in sumps or pump pits – direct burial is not permitted.
The liquid level in the reservoir must be at least 20 inches
above the water table.
The interstice must be filled from the low point in the
pipeline to minimize trapped air.
The evaluation was conducted in a Western Fiberglass, Inc.,
double-walled/coaxial flexible pipeline with an interstitial capacity of 1.64
gallons, an inside diameter of 1.5 inches, and a length of 200 feet.
Installers must be certified by both the piping and sensor
manufacturer.
Third-party evaluator certifies that this method performs equally well on the
present version (manufactured beginning March, 2006) as the previous version of
Western Fiberglass, Inc., double-walled/coaxial flexible pipeline.
Western Fiberglass,
Inc. |
Evaluator: Ken Wilcox
Associates |
1555 Copperhill Parkway |
Tel: (816) 443-2494 |
Santa Rosa, CA 95403 |
Date of Evaluation:
08/09/04 |
Tel: (707) 523-2050 |
|
E-Mail: sales@westernfg.com |
|
URL: www.westernfg.com |
|
|