Issue Date: November 22, 1995
Revision Date: September 20, 2011
Veeder-Root
(originally listed as Marley Pump Co.)
Red Jacket XLP
AUTOMATIC MECHANICAL LINE LEAK DETECTOR
Certification |
Leak rate of 3.0 gph with PD =
100% and PFA =0%. |
Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100
meeting ASTM D6751. |
Specification |
System tests pressurized
fiberglass and steel pipelines.
Tests are conducted at 15-22 psi. |
Pipeline
Capacity |
Maximum of 129 gallons. |
Waiting Time |
None between delivery and
testing.
None between dispensing and testing. |
Test Period |
Response time is 6 seconds. |
System
Features |
Permanent installation on
pipeline.
Automatic testing of pipeline.
Preset threshold.
Total vertical
rise of pipeline must not exceed 6 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
Calibration |
System must be checked annually
and, if necessary, calibrated in accordance with manufacturer's
instructions. |
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
Simsbury, CT 06070-2003
|
Date of Evaluation:
03/22/94,
03/24/11(letter)
|
Tel: (860) 651-2700
|
|
|