Issue Date: July 31, 2001
Revision Date: September 20, 2011
Veeder-Root
(originally listed as Marley Pump Co.)
Red Jacket
FX1DV, FX2DV Installed in the Big-Flow
(for Flexible Pipelines)
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Diesel,
biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100
meeting ASTM D6751. |
Specification |
System tests
pressurized flexible pipelines.
Tests are conducted at operating pressure. |
Pipeline
Capacity |
Maximum of 39.4
gallons. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing. |
Test
Period |
Response time is
less than 3 minutes. |
System
Features |
Permanent
installation on pipeline.
Automatic hourly testing of pipeline.
Preset threshold.
Total vertical
rise of pipeline must not exceed 11 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
Simsbury, CT 06070-2003
|
Dates of Evaluations:
03/15/94,
07/30/96, 03/11/99, 03/24/11(letter)
|
Tel: (860) 651-2700
|
|
|