Issue Date: November 22, 1995
Revision Date: June 24, 2002

Veeder-Root
(originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems)

PA02660000000 (Same as Veeder-Root 794390-700)

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

adsistor

 

Test Results:

 

unleaded gasoline

synthetic gasoline

JP-4 jet fuel

Detection time (min:sec)

7:46

N/A*

17:01

Fall time (min:sec)

2:38

N/A

3:05

Lower detection limit (ppm)

500

>1000

500

*See glossary.

Specificity Results:
Not activated:  n-hexane, toluene, xylene(s).

 

Veeder-Root

Evaluator:  Carnegie Mellon Research Institute

125 Powder Forest Dr.

Tel:  (412) 268-3495

Simsbury, CT 06070-2003

Date of Evaluation:  07/24/92

Tel:   (860) 651-2700  

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |