Issue Date: November 22, 1995
Revision Date: January 4, 2011
Veeder-Root
(originally listed as
Gilbarco Environmental Products and later as Marconi Commerce Systems)
PA02590XXX000,
(Same as Veeder-Root 0794390-401, 404, 407, 409),
PA02591144000, (Same as Veeder-Root 0794390-420, 460),
PA02592000010,
(Same as Veeder-Root 0794380-206)
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
|
Output
type: |
qualitative |
|
Sampling
frequency: |
continuous |
|
Operating
principle: |
float
switch |
Test Results:
|
|
unleaded
gasoline
|
synthetic
gasoline
|
|
PA02590XXX000
|
|
|
|
Response
time (min)
|
3.66
|
3.45
|
|
Recovery
time (min)
|
<1
|
<1
|
|
Product
activation height (cm)
|
1.28
|
1.27
|
|
Lower
detection limit (cm)
|
1.84
|
1.65
|
|
PA02591144000*
|
|
|
|
Response
time (min)
|
6.00
|
6.51
|
|
Recovery
time (min)
|
<1
|
<1
|
|
Product
activation height (cm)
|
3.67
|
3.62
|
|
Lower
detection limit (cm)
|
4.05
|
4.17
|
|
PA02592000010
|
|
|
|
Response
time (min)
|
8.19
|
8.49
|
|
Recovery
time (min)
|
<1
|
<1
|
|
Product
activation height (cm)
|
4.12
|
3.95
|
|
Lower
detection limit (cm)
|
4.67
|
4.36
|
*This sensor is identified as an interstitial sensor, but will function properly
in other containment areas such as containment sumps, contained risers and other
contained enclosures. This sensor must be installed at the lowest point of
the containment enclosure to insure early detection of liquids.
Specificity
Results (in addition to above):
Activated:
diesel, heating oil #2, water.
Comments:
Sensors
are reusable.
|
Veeder-Root
|
Evaluator:
Carnegie Mellon Research Institute
|
|
125 Powder Forest Dr.
|
Tel: (412) 268-3495
|
|
Simsbury, CT 06070-2003
|
Dates of Evaluations:
07/17/92, 04/22/98
|
|
Tel: (860) 651-2700
|
|
|
E-mail:
info@veeder.com |
|
|
URL: