Issue Date: September 11, 1998
Revision Date:
April 28, 2005
Veeder-Root
(originally listed as
Gilbarco Environmental Products and later as Marconi Commerce Systems)
EMC, EMC-PC,
EMC Enhanced, EMC-PC Enhanced,
LMS Environmental Management Consoles with Line
Leak Detector,
PA0263000100X (Same as Veeder-Root Series 8494),
PA0277000060X
(Same as Veeder-Root Series 8494)
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
Leak
Threshold |
2.5 gph for leak
rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.09 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel. |
Specification |
System tests
pressurized fiberglass and steel pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in
the pipeline. |
Pipeline
Capacity |
Maximum of 100
gallons. |
Waiting
Time |
None between
delivery and testing.
None between dispensing and testing for leak rate of 3.0 gph.
Minimum of 45 minutes between dispensing and testing for leak rate of 0.2
gph.
Minimum of 2 hours between dispensing and testing for leak rate of 0.1
gph. |
Test
Period |
Response time is
less than 1 minute for leak rate of 3.0 gph.
Response time is 30 to 45 minutes for leak rate of 0.2 gph.
Response time is 32 to 48 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is
declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Veeder-Root
|
Evaluator:
Midwest Research Institute
|
125 Powder Forest Dr.
|
Tel: (816) 753-7600
|
Simsbury, CT 06070-2003
|
Date of Evaluation:
05/08/96
|
Tel: (860) 651-2700
|
|
E-mail:
info@veeder.com |
|
URL:
www.veeder.com |
|
|