Issue Date: September 11, 1998
Revision Date:
April 28, 2005
Veeder-Root
(originally listed as
Gilbarco Environmental Products and later as Marconi Commerce Systems)
EMC
Environmental Management Console with Line Leak Detector,
Series PA0263000060X
(Same as Veeder-Root Series 8484)
(for Flexible Pipelines)
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
Leak
Threshold |
1.5 gph for leak
rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel. |
Specification |
System tests
pressurized flexible pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in
the pipeline. |
Pipeline
Capacity |
Maximum of 40.8
gallons. |
Waiting
Time |
None between
delivery and testing.
Minimum of 13 minutes between dispensing and testing for leak rate of 3.0
gph.
Minimum of 4 minutes to 1 hour, 9 minutes between dispensing and testing
for leak rate of 0.2 gph.
Minimum of 1 to 4 hours between dispensing and testing for leak rate of
0.1 gph. |
Test
Period |
Response time is
4 to 6 minutes for leak rate of 3.0 gph.
Response time is 40 minutes to 1 hour for leak rate of 0.2 gph.
Response time is 45 minutes to 1 hour, 15 minutes for leak rate of 0.1
gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor. |
System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is
declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Veeder-Root
|
Evaluator:
Midwest Research Institute
|
125 Powder Forest Dr.
|
Tel: (816) 753-7600
|
Simsbury, CT 06070-2003
|
Dates of Evaluations:
10/16/95,
01/13/97
|
Tel: (860) 651-2700
|
|
E-mail:
info@veeder.com |
|
URL:
www.veeder.com |
|
|