Issue Date: September 11, 1998
Revision Date: April 28, 2005

Veeder-Root
(originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems)

EMC Environmental Management Console with Line Leak Detector,
Series PA0263000060X (Same as Veeder-Root Series 8484)

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification

Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. 
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%. 
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.

Leak Threshold 1.88 gph for leak rate of 3.0 gph. 
0.17 gph for leak rate of 0.2 gph. 
0.05 gph for leak rate of 0.1 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel. 
Specification System tests pressurized fiberglass and steel pipelines. 
Tests are conducted at operating pressure. 
System will not function with a mechanical line leak detector installed in the pipeline.
Pipeline Capacity Maximum of 98.4 gallons.
Waiting Time None between delivery and testing. 
Minimum of 16 minutes between dispensing and testing for leak rate of 3.0 gph. 
Minimum of 45 minutes to 1 hour between dispensing and testing for leak rate of 0.2 gph. 
Minimum of 2 hours, 30 minutes between dispensing and testing for leak rate of 0.1 gph.
Test Period Response time is 28.8 seconds for leak rate of 3.0 gph. 
Response time is 32 to 48 minutes for leak rate of 0.2 gph. 
Response time is 18 minutes for leak rate of 0.1 gph. 
Test data are acquired and recorded by a microprocessor. 
Calculations are automatically performed by the microprocessor.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. Preset threshold. 
Single test to determine if pipeline is leaking. Pump shutdown (optional), message display and alarm activation if leak is declared.
Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.

 

Veeder-Root

Evaluator:  Midwest Research Institute

125 Powder Forest Dr.

Tel:  (816) 753-7600

Simsbury, CT 06070-2003

Dates of Evaluations:  08/07/91, 12/18/96

Tel:   (860) 651-2700  

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.