| Issue Date: November 22, 1995Revision Date: 
April 28, 2005
 
 Veeder-Root(originally listed as 
Gilbarco Environmental Products and later as Marconi Commerce Systems)
 EMC
Environmental Management Console with Line Leak Detector, Series PA02630000501
(Same as Veeder-Root Series 8475)
 AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR 
  
    | Certification | 
    Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
 Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA 
    = 0%.
 *Since leak 
    rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak
      Threshold | 1.5 gph for leak
      rate of 3.0 gph. 0.1 gph for leak rate of 0.2 gph.
 0.079 gph for leak rate of 0.1 gph.
 A pipeline system should not be declared tight if the test result
      indicates a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel,
      aviation fuel. |  
    | Specification | System tests
      pressurized fiberglass and steel pipelines. Tests are conducted at operating pressure.
 System will not function with a mechanical line leak detector installed in
      the pipeline.
 |  
    | Pipeline
      Capacity | Maximum of 158
      gallons. |  
    | Waiting
      Time | None between
      delivery and testing. Minimum between dispensing and testing depends on volume of product and
      temperature gradient which is determined by system's computer.
 |  
    | Test
      Period | Response time is
      14 seconds for leak rate of 3.0 gph. Response time is 6 minutes for leak rate of 0.2 gph.
 Response time is 14 minutes for leak rate of 0.1 gph.
 Test data are acquired and recorded by a microprocessor.
 Calculations are automatically performed by the microprocessor.
 |  
    | System
      Features | Permanent
      installation on pipeline. Automatic testing of pipeline. Preset threshold.
 Single test to determine if pipeline is leaking.
 Pump shutdown, message display, and alarm activation if leak is declared.
 |  
    | Calibration | System must be
      checked annually and, if necessary, calibrated in accordance with
      manufacturer's instructions. |    
  
    | 
      Veeder-Root | Evaluator: 
      Midwest Research Institute
      
      
       |  
    | 
      125 Powder Forest Dr. | Tel: 
      (816) 753-7600
      
      
       |  
    | 
      Simsbury, CT 06070-2003 | Date of
      Evaluation:  09/20/91
      
      
       |  
    | Tel:   (860) 651-2700 | Evaluator: 
      Ken Wilcox Associates
      
      
       |  
    | 
    E-mail:  
    info@veeder.com | Tel: 
      (816) 443-2494
      
      
       |  
    | 
    URL:  
    www.veeder.com | Date of
      Evaluation:  04/12/93
      
      
       |  |