Issue Date: November 19, 2010
Vista Precision Solutions, Inc.
(originally listed as Vista Research, Inc.)
Model HT-100
Monitoring Method and Line Tightness Test Method Version 2.1
Line Leak Detection Method for Airport Hydrant and Field Constructed Systems
Certification |
Leak rate of
0.00189% of line capacity (0.00189 gph per 1000 gallons of product) with PD = 95% and PFA = 5% for Version
2.1, (smallest leak rate for this evaluation, which was conducted on
a 160,000 gallon line at 150 psi, was 3.03 gph).
The USEPA has not set a minimum detectable leak rate for large diameter
pipeline systems (airport hydrant systems) at the time of this evaluation. |
Leak Threshold |
0.000945%
of line volume in gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds these thresholds. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4, biodiesel B6-B20 meeting ASTM D7467, biodiesel
B100 meeting ASTM D6751.
|
Specification |
System tests
fiberglass or steel piping.
|
Pipeline Capacity |
Maximum of
320,000 gallons. Minimum of 3,000 gallons. |
Waiting Time |
None between
delivery and testing.
None between dispensing and testing. |
Test Period |
Minimum 60 minutes after setup.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System Features |
System may be
permanently installed on pipelines to perform monitoring, or may be
transported and set up to perform line tightness testing.
A single 60-minute test is required consisting of a 30-minute
monitoring period at operating pressure, and a 30-minute monitoring period
at a lower pressure, approximately 30 psi.
System measures change in pressure and reports output quantity in gph, while
compensating for thermal effects.
Printed message and alarm activation if leak is declared.
|
Calibration |
System must be
calibrated prior to the initial test in accordance with manufacturer’s instructions.
|
Comments |
System is to be
used only on large bulk pipelines and airport hydrant fueling systems. |
Vista Precision Solutions, Inc. |
Evaluator: Ken Wilcox
Associates |
2350 Lindberg Loop |
Tel: (816) 443-2494 |
Richland, WA 99354 |
Date of
Evaluation: 08/25/07 |
Tel: (509) 943-2484 |
|
|