Issue Date: August 23, 1999
Revision Date: December 4, 2002
Vista Precision Solutions, Inc.
(originally listed as Vista Research, Inc.)
Model LT-100a
Hourly and Monthly Monitoring Method and Line Tightness Test Method Version 2.0
(Segmented Method)
Line Leak Detection Method for Airport Hydrant and Field Constructed Systems
Certification |
Leak rate of 3.0
gph with PD = 95% and PFA < 0.1% for Hourly Monitoring Method.
Leak rate of 0.2 gph with PD = 95% and PFA = 2.9% for Monthly Monitoring
Method.
The USEPA has not set a minimum detectable leak rate for large diameter
pipeline systems (airport hydrant systems) at the time of this evaluation. |
Leak Threshold |
2.936 gph for
leak rate of 3.0 gph.
0.136 gph for leak rate of 0.2 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4.
|
Specification |
System tests
fiberglass or steel piping.
Tests are conducted at operating pressure to a maximum of 200 psi.
|
Pipeline Capacity |
Maximum of 3,400
gallons. |
Waiting Time |
None between
delivery and testing.
None between dispensing and testing. |
Test Period |
Minimum of 15
minutes after setup and after pipeline is fully isolated.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System Features |
System may be
permanently installed on pipeline to perform hourly monitoring or monthly
monitoring, or may be transported and set up to perform line tightness
testing.
A single 15-minute test is required consisting of two 3-minute monitoring
segments at atmospheric pressure spaced 0 minutes apart, and two 3-minute
monitoring segments at operating pressure spaced 0 minutes apart.
Discrete test methods.
Preset threshold.
Printed message and alarm activation if leak is declared.
|
Calibration |
System must be
calibrated in accordance with manufacturer’s instructions during system
setup. |
Vista Precision Solutions, Inc. |
Evaluator: Ken Wilcox
Associates |
2350 Lindberg Loop |
Tel: (816) 443-2494 |
Richland, WA 99354 |
Date of Evaluation:
11/06/98 |
Tel: (509) 943-2484 |
|
|