| Issue Date: August 23, 1999Revision Date: December 4, 2002
 
 Vista Precision Solutions, Inc.(originally listed as Vista Research, Inc.)
 Model LT-100a 
Hourly and Monthly Monitoring Method and Line Tightness Test Method Version 2.0
(Segmented Method)
 Line Leak Detection Method for Airport Hydrant and Field Constructed Systems  
  
    | Certification | Leak rate of 3.0 
    gph with PD = 95% and PFA < 0.1% for Hourly Monitoring Method. Leak rate of 0.2 gph with PD = 95% and PFA = 2.9% for Monthly Monitoring 
    Method.
 The USEPA has not set a minimum detectable leak rate for large diameter 
    pipeline systems (airport hydrant systems) at the time of this evaluation.
 |  
    | Leak Threshold | 2.936 gph for 
    leak rate of 3.0 gph. 0.136 gph for leak rate of 0.2 gph.
 A pipeline system should not be declared tight if the test result indicates 
    a loss that equals or exceeds this threshold.
 |  
    | Applicability | Gasoline, diesel, 
    aviation fuel, fuel oil #4. |  
    | Specification | System tests 
    fiberglass or steel piping. Tests are conducted at operating pressure to a maximum of 200 psi.
 |  
    | Pipeline Capacity | Maximum of 3,400 
    gallons. |  
    | Waiting Time | None between 
    delivery and testing. None between dispensing and testing.
 |  
    | Test Period | Minimum of 15 
    minutes after setup and after pipeline is fully isolated. Test data are acquired and recorded by a microprocessor.
 Calculations are automatically performed by the microprocessor.
 |  
    | System Features | System may be 
    permanently installed on pipeline to perform hourly monitoring or monthly 
    monitoring, or may be transported and set up to perform line tightness 
    testing. A single 15-minute test is required consisting of two 3-minute monitoring 
    segments at atmospheric pressure spaced 0 minutes apart, and two 3-minute 
    monitoring segments at operating pressure spaced 0 minutes apart.
 Discrete test methods.
 Preset threshold.
 Printed message and alarm activation if leak is declared.
 |  
    | Calibration | System must be 
    calibrated in accordance with manufacturer’s instructions during system 
    setup. |    
  
    | Vista Precision Solutions, Inc. | Evaluator:  Ken Wilcox 
    Associates |  
    | 2350 Lindberg Loop | Tel:  (816) 443-2494 |  
    | Richland, WA 99354 | Date of Evaluation:  
    11/06/98 |  