Issue Date: February 13, 2024   

Veeder-Root

Veeder-Root BFX1V, BFX1DV in the Big Flow or Submersible Packer Manifold 

(for Rigid, Semi-rigid, Flexible and Hybrid Pipelines)

 

AUTOMATIC MECHANICAL LINE LEAK DETECTOR 

Certification

Leak rate of 3.0 gph with PD = 100% and PFA = 0%. 

Leak Threshold

3.0 gph at 10 psi equivalent.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.   

Applicability

For BFX1V: Gasoline/ethanol blends up through E85.
For BFX1DV: Biodiesel up through B100.

Specification 

System tests pressurized pipelines.
Tests are conducted at 8-16 psi. 

Pipeline Capacity 

Maximum of 425.84 gallons for rigid pipelines.
Maximum of 643 gallons for semi-rigid pipelines.
Maximum of 109.84 gallons for flexible pipelines.
Maximum of 1178.68 gallons for a combined rigid, semi-rigid, flexible hybrid pipeline with a minimum Bulk Modulus of 17,052 psi.

Waiting Time 

None between delivery and testing.
None between dispensing and testing.
Stabilization time up to 45 minutes may be required after dispensing when temperature extremes are present.

Test Period

Test Period Response time is typically less than 2-3 seconds in a line with no leak. 

System Features 

Permanent installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Total vertical rise of pipeline must not exceed 11 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. 

Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions 
 

 

 

Veeder-Root 

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT 06070-2003

Date of Evaluation:

Tel: (860) 651-2700

11/10/2023 
E-mail:   info@veeder.com  

 

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.