Issue Date: November 27, 2017

Veeder-Root

8601 Series
with Position Sensitive Pan/Sump Sensor 794380-323,
Position Sensitive Interstitial Sensor for Steel Tanks-333

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float/reed switch

 

Test Results:

Position Sensitive Pan/Sump Sensor 794380-323

 unleaded
gasoline

 diesel

water

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Threshold level (in)

1.4419

1.3851

1.3665
       
Position Sensitive Interstitial Sensor for Steel Tanks 794380-333      

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Threshold level (in)

1.364

1.281

1.231

 

Specificity Results (in addition to above):
Sensors will respond to any hydrocarbon liquid after its threshold is exceeded.

Comments:
Sensors are reusable. Sensor is easily removed, cleaned, and reinstalled.
The consoles in the 8601 Series are identical other than their name for marketing purposes. Each of the consoles within the series will perform identically.
The 8601 Series consists of the following derivatives: TLS4, TLS4B, TLS4c, TLS4i, and TLS-S1 consoles. The 794380-323 sensor is a position sensitive pan/sump sensor. This sensor detects the presence of fluid in the dispenser pan or containment sump. If the liquid level rises above the threshold of the sensor in the dispenser pan or containment sump, an alarm condition is generated. This would indicate there is liquid present in the dispenser pan or containment sump. The sensor is also position sensitive, meaning that if the sensor is not placed on the bottom of the dispenser pan or containment sump, an alarm would be generated warning that the sensor is no longer in the proper installation position.
The 794380-333 sensor is a position sensitive interstitial sensor for steel tanks. This sensor detects the presence of fluid in the interstice of a double-walled steel tank. If the liquid level rises above the threshold of the sensor in the interstice of a double-walled steel tank, an alarm condition is generated. condition is generated. This would indicate there is liquid present in the interstice area of the double-walled steel tank where the sensor is installed. The sensor is also position sensitive, meaning that if the sensor is not placed on the bottom of the dispenser pan or containment sump, an alarm would be generated warning that the sensor is no longer in the proper installation position.
For both sensors, console alarm is indicated by an audible alarm, a displayed message and a printed message (if the console is equipped with a printer.) The alarm is also recorded as part of Alarm History Report.          

Veeder-Root

Evaluator:  Ken Wilcox Associates, Inc

125 Powder Forest Dr.

1125 Valley Ridge Dr

Simsbury, CT 06070-2003

Grain Valley, MO 64029

Tel:  (860) 651-2700

Tel:  (816) 443-2494

E-mail:  info@veeder.com

Dates of Evaluations:  12/12/16