Issue Date: November 27, 2017

Veeder-Root

8601 Series
with Sump Sensor 794380-208, Sump Sensor 794380-209

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float/reed switch

 

Test Results:

Sump Sensor 794380-208,
794380-209

 unleaded
gasoline

 diesel

water

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Threshold level (in)

1.3448

1.3860

1.1983

 

Specificity Results (in addition to above):
Sensors will respond to any hydrocarbon liquid after its threshold is exceeded.

Comments:
Sensors are reusable. Sensor is easily removed, cleaned, and reinstalled.
The consoles in the 8601 Series are identical other than their name for marketing purposes. Each of the consoles within the series will perform identically.
The 8601 Series consists of the following derivatives: TLS4, TLS4B, TLS4c, TLS4i, and TLS-S1 consoles.
The 794380-208 and 794380-209 sensors are sump sensors with a cable length of 12’ and 30’, respectively. These sensors detect the presence of fluid in sumps. If the liquid level in the sump rises above the threshold of the sensor, an alarm condition is generated. This would indicate there is liquid present in the area where the sensor is installed.
For both sensors, console alarm is indicated by an audible alarm, a displayed message and a printed message (if the console is equipped with a printer). The alarm is also recorded as part of Alarm History Report          

Veeder-Root

Evaluator:  Ken Wilcox Associates, Inc

125 Powder Forest Dr.

1125 Valley Ridge Dr

Simsbury, CT 06070-2003

Grain Valley, MO 64029

Tel:  (860) 651-2700

Tel:  (816) 443-2494

E-mail:  info@veeder.com

Dates of Evaluations:  12/16/16

URL:  www.veeder.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.