Issue Date:
February 6, 2006
Revision Date: September 20, 2011
Veeder-Root
Red Jacket FX1V, FX2V in Big Flow or Packer
Manifold
(for Rigid and Flexible Pipelines)
AUTOMATIC MECHANICAL
LINE LEAK DETECTOR
Certification |
Leak rate of 3.0 gph with PD = 100% and PFA = 0%. |
Leak Threshold |
1.5 gph at 10 psi.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, ethanol blends up through E100. |
Specification |
System tests pressurized pipelines.
Tests are conducted at 8-12 psi. |
Pipeline Capacity |
Maximum of 416.7 gallons for rigid pipelines.
Maximum of 95.4 gallons for flexible pipelines. |
Waiting Time |
None between delivery and testing.
None between dispensing and testing.
Stabilization time up to 45 minutes may be required after dispensing when
temperature extremes are present. |
Test Period |
Response time is less than 5 minutes. |
System Features |
Permanent installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Total vertical rise of pipeline must not
exceed 11 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared.
|
Calibration |
System must be checked annually and, if necessary, calibrated
in accordance with manufacturer's instructions. |
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
125 Powder
Forest Dr.
|
Tel:
(816) 443-2494
|
Simsbury, CT
06070-2003
|
Dates of
Evaluations: 03/14/94, 03/22/94, 06/01/94, 11/21/05,
03/24/11(letter)
|
Tel: (860)
651-2700
|
|
E-mail:
info@veeder.com |
|
URL:
www.veeder.com |
|
|