Issue Date:  December 22, 2003
Revision Date:  April 8, 2011

Veeder-Root

TLS-350 Series, TLS-450 Series, EMC, EMC-PC, EMC Enhanced, EMC-PC Enhanced, and Red Jacket ProMax
with Magnetostrictive Sump Sensor Series 857060-xxx* and 857080-xxx*

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

 qualitative, discriminating

Sampling frequency:

 continuous

Operating principle:

 magnetostrictive probe with dual floats

Test Results:

24" Sump Sensor Series
857060-xxx* and 857080-xxx*

unleaded gasoline


diesel**


water

Gas on 7" of water
(fuel alarm in presence of water)

Diesel on 7" of water
(fuel alarm in presence of water)

Detection time (sec)

~ 10

~ 10

~ 10

~ 10

~ 10

Fall time (sec)

~ 10

~ 10

~ 10

~ 10

~ 10

Minimum product level (in)

1.368

1.329

1.614

1.116

1.101


*xxx
designates sensors in the 857060 and 857080 series containing: 857060 and 857080-101, -102, -111, -112, -121, -122, -211, -212, -221, and -222.

**Evaluations determined these sensors' responses to the liquids shown above.  Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded.  Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

Comments:
One sensor length (24”) was evaluated. Results are typical for the other sensors in the 857060-xxx and 857080-xxx series, regardless of length and programmability options.
All sensors are based on the use of a magnetostrictive sensor that is equipped with two floats. The lower float will only float on water. The upper float will float on fuel as well as water.
Results for the “water alarm” threshold will vary based upon programmed alarm levels.
The “fuel alarm” is based upon a fixed threshold and is not programmable.
Systems containing these sensors can be programmed to alarm continuously and to shut down the dispensing system.
Sensor will issue an alarm if raised from the bottom of the containment vessel.
Sensors are reusable.
Vendor claims sensors are easily removable, cleaned, and reinstalled if an alarm is triggered or for periodic testing.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations:  08/26/03, 05/17/04, 04/21/05, 05/27/05, 04/26/07, 03/03/08

Tel:  (860) 651-2700

 

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.