Issue Date: December 7, 2001
Revision Date: April 8, 2011

Veeder-Root

TLS-350, 350R Series, TLS-450 Series, Red Jacket ProMax with
Discriminating Interstitial Sensor 794380-343, Micro Sensor 794380-344

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative, discriminating (794380-343), non-discriminating (794380-344)

Sampling frequency:

continuous

Operating principle:

optical sensor and conductivity (794380-343), optical sensor (794380-344)

 

Test Results:

 

Discriminating Interstitial
Sensor 794380-343

 unleaded gasoline

 diesel*

 water

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Lower detection limit (in)

<0.1

<0.1

<0.1

 

Micro Sensor 794380-344**

unleaded gasoline

diesel*

water

E85

Used Oil

Detection time (min)

<1

<1

<1

<1 <1

Fall time (min)

<1

<1

<1

<1 <1

Lower detection limit (in)

<0.1

<0.1

<0.1

<0.1 <0.125

 

*Evaluations determined these sensors' responses to the liquids shown above.  Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded.  Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

**This sensor is identified as an interstitial sensor, but will function properly in other containment areas such as containment sumps, contained risers and other contained enclosures.  This sensor must be installed at the lowest point of the containment enclosure to insure early detection of liquids.

Specificity Results:
Evaluator claims both 794380-343 and 794380-344 sensors will respond in any liquid after the sensor threshold is exceeded.
Sensor 794380-343 is designed to discriminate between product and water.
Separate alarms are designed to be triggered for product and water.

Manufacturer’s Specifications:
Sensors 794380-343 and 794380-344 can be removed, cleaned, and reinstalled, for periodic testing, if an alarm is triggered or if service is necessary.
Sensor 794380-343 has no moving parts.
Sensor 794380-344 is designed for use in contained risers and the interstitial space of double-wall steel tanks.  When product or an open sensor (referred to as “Sensor Out”) is detected, an audible alarm is actuated, a message is displayed on the TLS-350 or TLS-350R console, and a printed message is generated if the console is equipped with a printer.  The alarms are also recorded as part of the TLS-350 or TLS-350R “Alarm History Report”.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations:  05/10/01, 02/02/06, 03/03/08, 08/05/10

Tel:  (860) 651-2700

 

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.