Issue Date: November 22, 1995
Revision Date: June 20, 2008

Veeder-Root

ILS-350, TLS-350 Series, TLS-450 Series, Red Jacket ProMax with Adsistor Vapor Probe 794390-700

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

adsistor

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

JP-4 jet fuel

Detection time (min:sec)

7:46

N/A*

17:01

Fall time (min:sec)

2:38

N/A

3:05

Lower detection limit (ppm)

500

>1000

500

*See Glossary.

Specificity Results:
Not Activated:  n-hexane, toluene, xylene(s).
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

 

Veeder-Root

Evaluator:  Carnegie Mellon Research Institute

125 Powder Forest Dr.

Tel:  (412) 268-3495

Simsbury, CT 06070-2003

Date of Evaluation:  07/24/92

Tel:  (860) 651-2700

Evaluator: Ken Wilcox Associates

E-mail:  info@veeder.com

Tel: (816) 443-2494

URL:  www.veeder.com

Date of Evaluation: 03/03/08
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.