Issue Date:  November 22, 1995
Revision Date:  June 20, 2008

Veeder-Root

350 Series, TLS-450 Series, Red Jacket ProMax UST Monitoring Systems Models ILS-350, TLS-350, 350R, 350PC, 350RPC
with Groundwater Sensors 794380-621, 622, 624

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

Detection time (min:sec)

8:55

6:18

Fall time (min:sec)

54:50

26:02

Lower detection limit (cm)

0.02

0.02

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Calibration:
Sensor must be checked annually for operability or in accordance with manufacturer’s instructions and, if necessary, calibrated or replaced.

Comments:
Sensors are reusable.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

 

Veeder-Root

Evaluator:  Carnegie Mellon Research Institute

125 Powder Forest Dr.

Tel:  (412) 268-3495

Simsbury, CT  06070-2003

Dates of Evaluations:  11/20/91, 07/28/92

Tel:  (860) 651-2700

Evaluator: Ken Wilcox Associates

E-mail:  info@veeder.com

Tel: (816) 443-2494

URL:  www.veeder.com

Date of Evaluation: 03/03/08
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.