Issue Date: November 22, 1995
Revision Date: June 10, 2013

Veeder-Root

ILS-350, TLS-300C, 300i, 300PC, 350, 350PC, 350R, 350RPC, TLS-450 Series, Red Jacket ProMax and ProPlus
with Solid-State Pan/Sump Sensor 794380-321, 351,
Piping Sump Sensor 794380-208, 209,
Micro Sensor 794380-340

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float/reed switch (794380-208, 209), optical (794380-321, 340, 351)

 

Test Results:

 

unleaded gasoline

diesel*

water

used oil

Solid-State Pan/Sump Sensor 794380-321, 351

 

 

 

 

Minimum product thickness (cm)

2.60

2.50

2.60

N/D****

Precision (cm)

0.010

0.010

0.010

N/D****

Detection time (sec)

<1

<1

<1

N/D****


Piping Sump Sensor 794380-208**, 209

       

Minimum product level (cm)

3.51

3.40

3.03

3.76

Precision (cm)

0.011

0.011

0.011

.036

Detection time (sec)

<1

<1

<1

<1


Micro Sensor 794380-340***

 

 

 

 

Minimum product thickness (cm)

0.51

0.46

0.48

N/D****

Precision (cm)

0.011

0.007

0.007

N/D****

Detection time (sec)

<1

<1

<1

N/D****

 

*Evaluations determined these sensors' responses to the liquids shown above.  Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded.  Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

**This sensor is identified as an interstitial sensor, but will function properly in other containment areas such as containment sumps, contained risers and other contained enclosures.  This sensor must be installed at the lowest point of the containment enclosure to insure early detection of liquids.  Results stated for used oil applicable to this sensor only.

*** Micro Sensor 794380-340 is not supported by TLS 450 series console.

****See Glossary

 

Comments:
Sensors are reusable.
208 and 209 sensors are also compatible with 300 series.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.
 


 

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations: 10/20/94, 05/22/02, 03/03/08, 04/15/11

Tel:  (860) 651-2700

 

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.