Issue Date: August 28, 1998
Revision Date: April 8, 2011

Veeder-Root

TLS-300, 300i, TLS-350 Series, TLS-450 Series, Red Jacket ProMax and ProPlus with
Discriminating Dispenser Pan Sensor 794380-322,
Discriminating Containment Sump Sensor 794380-352

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable, reed switch/float

 Test Results:

 

polymer strip

float switch

 

unleaded gasoline

diesel*

water

Discriminating Dispenser Pan

     

Sensor 794380-322

 

 

high**

low**

Response time (sec)

~10 min

2-12 hrs

<1

<1

Recovery time (sec)

N/A***

N/A

<1

<1

Lower detection limit - height (in)

N/D***

N/D

7.66

1.37

Lower detection limit - thickness (in)

0.005

0.005

N/A

N/A


Discriminating Containment Sump

 

 

 

 

Sensor 794380-352

 

 

 

 

Response time (sec)

~10 min

2-12 hrs

<1

<1

Recovery time (sec)

N/A

N/A

<1

<1

Lower detection limit - height (in)

N/D

N/D

12.28

1.35

Lower detection limit - thickness (in)

0.005

0.005

N/A

N/A

 

*Evaluations determined these sensors' responses to the liquids shown above and those indicated in the following section.  Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded.  Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

**The "high" and "low" refer to high and low level alarm points of float switch sensors.
*** See glossary.

Specificity Results (in addition to above):
Activated:  synthetic gasoline,  jet-A fuel, n-hexane, toluene, xylene(s)
Not activated:  water (polymer strip only)

Comments:
Polymer strip must be air dried after exposure to unleaded fuel.
Polymer strips must be cleaned with solvent and dried after exposure to diesel.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT 06070-2003

Dates of Evaluations:  01/02/95, 06/23/97, 04/20/98, 03/03/08

Tel:  (860) 651-2700

 

E-mail:  info@veeder.com

 

URL:  www.veeder.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.