| Issue Date: November 22, 1995Revision Date: September 20, 2011
 
 Veeder-Root 
 TLS 350, 
350PC, 350R, 350RPC, 350Plus,  Red Jacket ProMax  Line Leak Detector, with Series 8484 
PLLD and TLS 450 Series 8590 DPLLD AUTOMATIC ELECTRONIC LINE LEAK 
DETECTOR  
  
    | Certification | 
    Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
 Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA 
    = 0%.
 *Since leak 
    rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak Threshold | 1.88 gph for leak 
    rate of 3.0 gph. 0.17 gph for leak rate of 0.2 gph.
 0.05 gph for leak rate of 0.1 gph.
 A pipeline system should not be declared tight if the test result indicates 
    a loss that equals or exceeds this threshold.
 |  
    | Applicability | 
	Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, 
	biodiesel B100 meeting ASTM D6751. 
 |  
    | Specification | System tests 
    pressurized fiberglass and steel pipelines. Tests are conducted at operating pressure.
 System will not function with a mechanical line leak detector installed in 
    the pipeline.
 |  
    | Pipeline Capacity | Maximum of 98.4 
    gallons. |  
    | Waiting Time | None between 
    delivery and testing. Minimum of 16 minutes between dispensing and testing for leak rate of 3.0 
    gph.
 Minimum of 45 minutes to 1 hour between dispensing and testing for leak rate 
    of 0.2 gph.
 Minimum of 2 hours, 30 minutes between dispensing and testing for leak rate 
    of 0.1 gph.
 |  
    | Test Period | Response time is 
    28.8 seconds for leak rate of 3.0 gph. Response time is 32 to 48 minutes for leak rate of 0.2 gph.
 Response time is 18 minutes for leak rate of 0.1 gph.
 Test data are acquired and recorded by a microprocessor.
 Calculations are automatically performed by the microprocessor.
 |  
    | System Features | TLS 
    350 console can only be used with Series 8484 PLLD. TLS 450 console 
    can only be used with Series 8590 DPLLD. When using Red 
	Jacket BIG-FLO Submersible Pump Models P100H1, P200H1, P200H3, P300H3, P500H3, the PLLD 
	only performs 3.0 gph testing and not precision (0.2 and 0.1gph) testing. {USER DEFINED} 
	pipe type must be selected under the PLLD setup to allow precision (0.2 and 
	0.1 gph) testing with Red Jacket BIG-FLO Submersible Pump Models:  
	MAXXUM MSP300, MAXXUM MSP500. Total vertical 
	rise of pipeline must not exceed 11 feet above transducer. Permanent 
    installation on pipeline. Automatic testing of pipeline.
 Preset threshold.
 Single test to determine if pipeline is leaking.
 Pump shutdown (optional), message display and alarm activation if leak is 
    declared.
 |  
    | Calibration | System must be 
    checked annually and, if necessary, calibrated in accordance with 
    manufacturer's instructions. |    
  
    | Veeder-Root | 
    Evaluator:  Midwest Research Institute |  
    | 125 
    Powder Forest Dr. | Tel:  
    (816) 753-7600 |  
    | Simsbury, 
    CT  06070-2003 | Dates of 
    Evaluations:  08/07/91, 12/18/96 |  
    | Tel:  
    (860) 651-2700 | 
    Evaluator: Ken Wilcox 
    Associates |  
    | 
    E-mail:  
    info@veeder.com | Tel: (816) 
    443-2494 |  
    | 
    URL:  
    www.veeder.com | 
    Date of Evaluation:  
    02/27/08, 7/28/09,  
	03/24/11(letter) |  |