Issue Date: November 22, 1995
Revision Date: September 20, 2011
Veeder-Root
TLS 350,
350PC, 350R, 350RPC, 350Plus, Red Jacket ProMax Line Leak Detector, with Series 8484
PLLD and TLS 450 Series 8590 DPLLD
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
Leak Threshold |
1.88 gph for leak
rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467,
biodiesel B100 meeting ASTM D6751.
|
Specification |
System tests
pressurized fiberglass and steel pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in
the pipeline. |
Pipeline Capacity |
Maximum of 98.4
gallons. |
Waiting Time |
None between
delivery and testing.
Minimum of 16 minutes between dispensing and testing for leak rate of 3.0
gph.
Minimum of 45 minutes to 1 hour between dispensing and testing for leak rate
of 0.2 gph.
Minimum of 2 hours, 30 minutes between dispensing and testing for leak rate
of 0.1 gph. |
Test Period |
Response time is
28.8 seconds for leak rate of 3.0 gph.
Response time is 32 to 48 minutes for leak rate of 0.2 gph.
Response time is 18 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
System Features |
TLS
350 console can only be used with Series 8484 PLLD.
TLS 450 console
can only be used with Series 8590 DPLLD.
When using Red
Jacket BIG-FLO Submersible Pump Models P100H1, P200H1, P200H3, P300H3, P500H3, the PLLD
only performs 3.0 gph testing and not precision (0.2 and 0.1gph) testing.
{USER DEFINED}
pipe type must be selected under the PLLD setup to allow precision (0.2 and
0.1 gph) testing with Red Jacket BIG-FLO Submersible Pump Models:
MAXXUM MSP300, MAXXUM MSP500.
Total vertical
rise of pipeline must not exceed 11 feet above transducer.
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is
declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Veeder-Root |
Evaluator: Midwest Research Institute |
125
Powder Forest Dr. |
Tel:
(816) 753-7600 |
Simsbury,
CT 06070-2003 |
Dates of
Evaluations: 08/07/91, 12/18/96 |
Tel:
(860) 651-2700 |
Evaluator: Ken Wilcox
Associates |
E-mail:
info@veeder.com |
Tel: (816)
443-2494 |
URL:
www.veeder.com |
Date of Evaluation:
02/27/08, 7/28/09,
03/24/11(letter) |
|