| Issue Date: November 22, 1995Revision Date: September 20, 2011
 
 Veeder-Root 
 TLS-350, 
350PC, 350R, 350RPC, 350Plus, Red Jacket ProMax  Line Leak Detector, Series 8475 
VLLD(for Flexible Pipelines)
 AUTOMATIC ELECTRONIC LINE LEAK 
DETECTOR  
  
    | Certification | 
    Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%. Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
 Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA 
    = 0%.
 *Since leak 
    rate varies as a function of pressure, this leak rate and pressure were 
    certified using an equivalent leak rate and pressure, in accordance with an 
    acceptable protocol.
 |  
    | Leak Threshold | 1.5 gph for leak 
    rate of 3.0 gph. 0.1 gph for leak rate of 0.2 gph.
 0.079 gph for leak rate of 0.1 gph.
 A pipeline system should not be declared tight if the test result indicates 
    a loss that equals or exceeds this threshold.
 |  
    | Applicability | 
	Gasoline, diesel, aviation fuel, ethanol blends up through E100, biodiesel blends B6-B20 meeting ASTM D7467, 
	biodiesel B100 meeting ASTM D6751.  |  
    | Specification | System tests 
    pressurized flexible pipelines. Tests are conducted at operating pressure.
 System will not function with a mechanical line leak detector installed in 
    the pipeline.
 |  
    | Pipeline Capacity | Maximum of 49.6 
    gallons. |  
    | Waiting Time | None between 
    delivery and testing. Minimum between dispensing and testing depends on volume of product and 
    temperature gradient which is determined by system's computer.
 |  
    | Test Period | Response time is 
    1 minute for leak rate of 3.0 gph. Response time is 45 minutes to 8 hours, 51 minutes for leak rate of 0.2 gph.
 Response time is 1 hour, 12 minutes to 12 hours, 54 minutes for leak rate of 
    0.1 gph.
 Test data are acquired and recorded by a microprocessor.
 Calculations are automatically performed by the microprocessor.
 |  
    | System Features | Permanent 
    installation on pipeline. Automatic testing of pipeline.
 Preset threshold.
 If 
	pump side leak testing is required, total vertical rise of pipeline must not 
	exceed 8 feet above VLLD Controller.Single test to determine if pipeline is leaking.
 Pump shutdown, message display and alarm activation if leak is declared.
 |  
    | Calibration | System must be 
    checked annually and, if necessary, calibrated in accordance with 
    manufacturer's instructions. |    
  
    | Veeder-Root | 
    Evaluator:  Ken Wilcox Associates |  
    | 125 
    Powder Forest Dr. | Tel:  
    (816) 443-2494 |  
    | 
    Simsbury, CT  06070-2003 | Date of 
    Evaluation:  08/04/93, 03/24/11(letter) |  
    | Tel:  
    (860) 651-2700 |   |  |