Issue Date: November 22, 1995
Revision Date: November 28, 2012
Vaporless Manufacturing
Vaporless
99LD-3000,
LD-3000, 99 LD-3000S, LD-3000S
(for Rigid, Flexible, or Hybrid Combination of Rigid and Flexible Pipelines)
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel.
|
Specification |
System tests
pressurized steel and fiberglass pipelines and combination of rigid and
flexible pipelines.
Tests are conducted at operating pressure. |
Pipeline Capacity |
Maximum of
404
gallons for steel and fiberglass pipelines
Maximum of 96
gallons for flexible pipelines
Maximum combined
capacity is 500 gallons, not to exceed the above individual capacity
limitations for combination rigid or flexible pipelines. |
Waiting Time |
None between
dispensing and testing. |
Test Period |
Response time is
9 seconds. |
System Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
LD3000 - restricted flow to dispenser if leak is declared.
LD3000S - pump shutoff if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Comments |
Functionality and
operability of the 99 LD-3000 are unchanged by installation of the Leak
Detection Sensor (piston switch) that supports the VMI ISM-4080 and ISM-4081
Integrated Shutdown Module. |
Vaporless Manufacturing |
Evaluator: Ken Wilcox
Associates |
8700 East Long Mesa Drive |
Tel: (816) 443-2494 |
Prescott Valley, AZ 86314 |
Date of
Evaluation: 08/20/93, 4/17/06 |
Tel: (928)
775-5191 |
|
|