Issue Date: November 22, 1995
Revision Date: November 14, 1997
Vaporless Manufacturing
Vaporless
LD-2000, LD-2000S
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
Leak Threshold |
1.7 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel.
|
Specification |
System tests
pressurized fiberglass or steel pipelines.
Tests are conducted at operating pressure. |
Pipeline Capacity |
Maximum of 129
gallons. |
Waiting Time |
None between
dispensing and testing.
None between delivery and testing. |
Test Period |
Response time is
5 seconds. |
System Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
LD2000 - restricted flow to dispenser if leak is declared.
LD2000S - pump shutoff if leak is declared. |
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Vaporless Manufacturing |
Evaluator: Ken Wilcox
Associates |
8700 East Long Mesa Drive |
Tel: (816) 443-2494 |
Prescott Valley, AZ 86314 |
Dates of
Evaluation: 11/19/90 |
Tel:
(928) 775-5191 |
|
|