Issue Date: January 27, 2021
TURPAK Electromagnetic
Fuel Supply Systems, Inc.
TURPAK SIR Vision EYE v1.0
STATISTICAL INVENTORY RECONCILIATION TEST METHOD (QUANTITATIVE)
Certification | Leak rate of 0.2
gph with PD > 99.5% and PFA < 0.5% Leak rate of 0.1 gph with PD > 98.5% and PFA < 1.5% |
Leak Threshold | 0.1 gph for leak
rate of 0.2 gph 0.05 gph for leak rate of 0.1 gph A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the threshold of the version selected Gains (water ingress) are analyzed and evaluated on an individual basis |
Applicability | Gasoline, diesel, aviation fuel, kerosene |
Tank Capacity | Maximum of 30,000
gallons for single tank Maximum of 30,000 gallons cumulative capacity for siphoned tank systems with no more than 3 tanks in system |
Throughput | Maximum monthly throughput of 54,930 gallons |
Data Requirement | Minimum of 30 days of product level and flow through data |
Comments | 34% of data sets
evaluated were from siphoned tank systems 66% of data sets evaluated used from single tank systems Of 44 data sets submitted for evaluation, all were analyzed with conclusive results Median monthly throughput of tanks evaluated was 8,897 gallons Data sets evaluated were supplied by evaluator The SIR system, TURPAK SIR Vision EYE v1.0 belonging to Turpak Corporation was tested on data from one tank system at a time. Upon completion of each tank test, the results were transmitted back to SSG Associates |
TURPAK SIR Vision EYE v1.0 |
Evaluator:
S.S.G. Associates |
Address : Merkez Mahallesi Erseven Sokak No:8/1/4 |
Tel:
(662) 234-1179 |
Kağıthane 34406/ ISTANBUL
|
Dates
of Evaluations:
November 2020
|
Phone: +90 212 3154100 | |
E-mail: Suleyman ERDOGAN | |
serdogan@turpak.com.tr |
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |
Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations. For full details, please refer to our expanded "DISCLAIMER"
page.