TURPAK SIR Vision EYE v1.0

Issue Date: January 27, 2021

TURPAK Electromagnetic Fuel Supply Systems, Inc.

TURPAK SIR Vision EYE v1.0

STATISTICAL INVENTORY RECONCILIATION TEST METHOD (QUANTITATIVE)

Certification Leak rate of 0.2 gph with PD > 99.5% and PFA < 0.5%
Leak rate of 0.1 gph with PD > 98.5% and PFA < 1.5%
Leak Threshold 0.1 gph for leak rate of 0.2 gph
0.05 gph for leak rate of 0.1 gph
A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the threshold of the version selected Gains (water ingress) are analyzed and evaluated on an individual basis
Applicability Gasoline, diesel, aviation fuel, kerosene
Tank Capacity Maximum of 30,000 gallons for single tank
Maximum of 30,000 gallons cumulative capacity for siphoned tank systems with no more than 3 tanks in system
Throughput Maximum monthly throughput of 54,930 gallons
Data Requirement Minimum of 30 days of product level and flow through data
Comments 34% of data sets evaluated were from siphoned tank systems
66% of data sets evaluated used from single tank systems
Of 44 data sets submitted for evaluation, all were analyzed with conclusive results
Median monthly throughput of tanks evaluated was 8,897 gallons Data sets evaluated were supplied by evaluator

The SIR system, TURPAK SIR Vision EYE v1.0 belonging to Turpak Corporation was tested on data from one tank system at a time. Upon completion of each tank test, the results were transmitted back to SSG Associates

 

TURPAK SIR Vision EYE v1.0

Evaluator:  S.S.G. Associates

Address : Merkez Mahallesi Erseven Sokak No:8/1/4

Tel:  (662) 234-1179

Kağıthane 34406/ ISTANBUL

Dates of Evaluations:  November 2020

Phone: +90 212 3154100  
E-mail: Suleyman ERDOGAN  

serdogan@turpak.com.tr

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.