Issue Date: November 22, 1995
Revision Date: April 17, 2003
Tyco
Thermal Controls LLC
(originally listed
as Raychem Corp.)
TraceTek
Alarm and Locator Modules with
TT502, TT5000, TT3000 Fuel Sensing Cable
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
and
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Output
type:
|
qualitative
|
Sampling
frequency:
|
continuous
|
Operating
principle:
|
electrical conductivity
|
Test
Results:
|
unleaded
gasoline
|
|
TT502
|
1/3
MER*
334
m
|
2/3
MER
665
m
|
MER
995
m
|
|
Response
time (min)
|
22.11
|
17.13
|
19.42
|
|
Product
activation height (cm)
|
1.53
|
1.53
|
1.53
|
|
Detection
length (cm)
|
61
|
61
|
61
|
|
Lower
detection limits (cm)
|
|
|
|
|
Product activation height
|
N/D*
|
N/D
|
0.77
|
|
Detection length
|
N/D
|
N/D
|
10
|
|
TT5000
|
1/3
MER
508
m
|
2/3
MER
1016
m
|
MER
1524
m
|
|
Response
time (min)
|
12.02
|
9.18
|
7.51
|
|
Product
activation height (cm)
|
0.74
|
0.74
|
0.74
|
|
Detection
length (cm)
|
30.5
|
30.5
|
30.5
|
|
Lower
detection limits (cm)
|
|
|
|
|
Product activation height
|
N/D
|
N/D
|
0.74
|
|
Detection length
|
N/D
|
N/D
|
10
|
|
|
3%
by weight salt in water
|
other
solutions**
|
TT3000
|
1/3
MER
508
m
|
2/3
MER
1016
m
|
MER
1524
m
|
MER
1524
m
|
Response
time (min)
|
<1
|
<1
|
<1
|
<1
|
Recovery
time (min)
|
<1
|
<1
|
<1
|
<1
|
Product
activation height (cm)
|
<0.3
|
<0.3
|
<0.3
|
<0.3
|
Detection
length (cm)
|
<15.2
|
<15.2
|
<15.2
|
<15.2
|
Lower
detection limits (cm)
|
|
|
|
|
Product activation height
|
N/D
|
N/D
|
<0.3
|
N/D
|
Detection length
|
N/D
|
N/D
|
<5.08
|
N/D
|
*
See glossary.
**
5% by volume oil in 3% by weight salt water, 10% by volume oil in 3% by weight
salt water, 0.1 M hydrochloric acid (HCl), 0.1M
sodium hydroxide (NaOH).
Specificity
Results (in addition to above for TT502 and
TT5000):
Activated: synthetic
gasoline, diesel, heating oil #2, jet-A fuel (TT5000 only).
Not
Activated: water.
Specificity
Results (in addition to above for TT3000):
Activated:
water
Not
Activated: unleaded
gasoline, synthetic gasoline, diesel, JP-8 fuel.
Comments:
Evaluation
also covered quantitative leak location.
TT502,
TT5000 Fuel Sensing cable is not reusable.
Lower
detection limit is calculated at MER only, and cable is assumed to be equally or
more sensitive at shorter lengths.
Tyco Thermal Controls
LLC
|
Evaluator:
Carnegie Mellon Research Institute
|
300 Constitution Dr.
|
Tel: (412) 268-3495
|
Menlo Park, CA 94025-1164
|
Dates of Evaluation:
05/15/92, 12/20/95,
02/20/98
|
Tel: (800) 545-6258
|
|
|