| Issue Date: August 27, 2007 
 
Tyco Thermal Controls LLC 
TraceTek Alarm and 
Locator Moduleswith TT-FFS Fast Fuel Sensor
 
INTERSTITIAL 
DETECTOR (LIQUID-PHASE)and
 OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
 Detector:
 
 
  
    | Output
      type: | qualitative 
 |  
    | Sampling
      frequency: | continuous
 |  
    | Operating
      principle: | electrical conductivity
        |  
Test Results:
 
  
    | 
    TT-FFS  (.005" fuel on 
    water) | 
    synthetic gasoline | 
    diesel | 
    jet-A fuel | 
    crude oil |  
    | 
    Response time (min:sec) | 
    <1 | 
    <1 | 
    <1 | 
    2:33 |  
    | 
    TT-FFS  (.024" fuel on flat 
    surface) | 
      | 
      | 
      | 
      |  
    | 
    Response time (min) | 
    <1 | 
    <1 | 
    <1 | 
    11 |  
Specificity Results:
Activated:  
synthetic gasoline, diesel, 
jet-A fuel, crude oil.
 Probability of Detection:  
100% for all tested liquids with 
92% to 100% confidence interval.
 Not 
Activated:  water
 
Comments:
All data points 
are the average of 6 samples.
 Dry surface fuel layer depth estimated at .005" for gasoline, diesel and jet-A, 
.024" for crude oil.
 Fuel layer for fuel floating on water estimated to be .005" for all tests.
 Sensors can be cleaned and reset by soaking in naphtha and allowing them to dry 
in the air for 1 hour.
 Sensors that do not reset must be replaced.
 Sensor can be 
periodically tested with naphtha.  Manufacturer recommends 6 month interval.
   
  
    
      | Tyco Thermal Controls 
      LLC | Evaluator: 
      Ken Wilcox Associates |  
      | 300 Constitution Dr. | Tel: 
      (816) 443-2494 |  
      | Menlo Park, CA 
      94025-1164 | Date of Evaluation: 
      9/06 |  
      | Tel:  (800) 545-6258 |  |  
      |  |  |  
      |  |  |    |