Issue Date: August 27, 2007
Tyco Thermal Controls LLC
TraceTek Alarm and
Locator Modules
with TT-FFS Fast Fuel Sensor
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
and
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Output
type:
|
qualitative
|
Sampling
frequency:
|
continuous
|
Operating
principle:
|
electrical conductivity
|
Test Results:
TT-FFS (.005" fuel on
water) |
synthetic gasoline |
diesel |
jet-A fuel |
crude oil |
Response time (min:sec) |
<1 |
<1 |
<1 |
2:33 |
TT-FFS (.024" fuel on flat
surface) |
|
|
|
|
Response time (min) |
<1 |
<1 |
<1 |
11 |
Specificity Results:
Activated:
synthetic gasoline, diesel,
jet-A fuel, crude oil.
Probability of Detection:
100% for all tested liquids with
92% to 100% confidence interval.
Not
Activated: water
Comments:
All data points
are the average of 6 samples.
Dry surface fuel layer depth estimated at .005" for gasoline, diesel and jet-A,
.024" for crude oil.
Fuel layer for fuel floating on water estimated to be .005" for all tests.
Sensors can be cleaned and reset by soaking in naphtha and allowing them to dry
in the air for 1 hour.
Sensors that do not reset must be replaced.
Sensor can be
periodically tested with naphtha. Manufacturer recommends 6 month interval.