Issue Date: August 27, 2007


Tyco Thermal Controls LLC

TraceTek Alarm and Locator Modules
with TT-FFS Fast Fuel Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)
and
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)


Detector:
 

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity  

Test Results:
 

TT-FFS  (.005" fuel on water)

synthetic gasoline

diesel

jet-A fuel

crude oil

Response time (min:sec)

<1

<1

<1

2:33

TT-FFS  (.024" fuel on flat surface)

 

 

 

 

Response time (min)

<1

<1

<1

11

Specificity Results:
Activated: 
synthetic gasoline, diesel, jet-A fuel, crude oil.
Probability of Detection:  100% for all tested liquids with 92% to 100% confidence interval.
Not Activated:  water

Comments:
All data points are the average of 6 samples.
Dry surface fuel layer depth estimated at .005" for gasoline, diesel and jet-A, .024" for crude oil.
Fuel layer for fuel floating on water estimated to be .005" for all tests.
Sensors can be cleaned and reset by soaking in naphtha and allowing them to dry in the air for 1 hour. 
Sensors that do not reset must be replaced.
Sensor can be periodically tested with naphtha.  Manufacturer recommends 6 month interval.

 

Tyco Thermal Controls LLC Evaluator:  Ken Wilcox Associates
300 Constitution Dr. Tel:  (816) 443-2494
Menlo Park, CA 94025-1164 Date of Evaluation:  9/06
Tel:  (800) 545-6258  
   
   

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.