Issue Date: November 22, 1995
Revision Date: November 6, 1997

Tokheim Corp.

Tokheim Pressure Monitor, Models PM 101, 585A-PM

AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%.
Leak Threshold 2.25 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel. 
Specification System tests pressurized fiberglass and steel pipelines. 
Tests are conducted at 150% operating pressure.
Pipeline Capacity Maximum of 78 gallons.
Waiting Time None between delivery and testing. 
None between dispensing and testing.
Test Period Response time is 4 seconds.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. 
Preset threshold. 
Single test to determine if pipeline is leaking. 
Restricted flow to dispenser if leak is declared.
Calibration System must be checked semi-annually and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments No longer manufactured by Tokheim Corporation.

 

Tokheim Corp.

Evaluator:  Vista Research

U. S. Division is bankrupt as of 02/2003.

Tel:  (415) 966-1171

Website:  www.tokheim.com

Date of Evaluation:  11/02/90

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.