Issue Date: November 22, 1995
Revision Date: August 23, 1999
Tidel
Engineering, Inc.
Tidel
Detector #301-0324-001, #301-0325-001, #301-0326-001, #301-0326-002
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Test Results:
Tidel Detector #301-0324-001,
#301-0325-001
|
unleaded
gasoline
|
synthetic
gasoline
|
JP-4
jet fuel
|
Detection
time (sec)
|
2
|
2
|
1
|
Fall
time (sec)
|
1
|
2
|
2
|
Lower
detection limit (cm)
|
0.16-0.32
|
0.16-0.32
|
0.16-0.32
|
Tidel Detector #301-0326-001,
#301-0326-002
|
|
|
|
Detection
time (sec)
|
4
|
7
|
2
|
Fall
time (sec)
|
3
|
4
|
4
|
Lower
detection limit (cm)
|
0.08-0.32
|
0.08-0.32
|
0.08-0.32
|
Specificity
Results (in addition to above):
Activated:
n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Manufacturer’s
specifications:
Tidel Detector #301-0324-001
|
Application:
|
Liquid
sensor, water, used in 4" monitoring well.
|
Sensor:
|
Magnetism
and conductivity pins.
|
Detection
Range:
|
1/8"
floating product on groundwater or 1.5" free product.
|
Tidel Detector #301-0325-001
|
Application:
|
Liquid
sensor, water or hydrocarbon used in reservoir, sump or pipeline trench.
|
Sensor:
|
Magnetism
and conductivity pins.
|
Detection
Range:
|
1/8"
floating product on groundwater or 1.5" free product.
|
Tidel Detector #301-0326-001
|
Application:
|
Liquid
sensor, water, used in 2" monitoring well.
|
Sensor:
|
Magnetism
and conductivity pins.
|
Detection
Range:
|
1/8"
floating product on groundwater or 2.5" free product.
|
Tidel Detector #301-0326-002
|
Application:
|
Liquid
sensor, water, used in annulus of double-wall steel tanks.
|
Sensor:
|
Magnetism
and conductivity pins.
|
Detection
Range:
|
1/8"
floating product on groundwater or 2.5" free product.
|
Comments:
Sensors
are reusable.
Lower
detection limit has been statistically determined to be within the range
specified above.
Tidel
Engineering, Inc.
|
Evaluator:
Radian Corp.
|
2025 West Beltline Road, #114 |
Tel:
(512) 454-4797
|
Carrollton
,
TX
75006
|
Date
of Evaluation:
07/08/91
|
Tel:
(800) 678-7577
|
|
|