Issue Date: November 22, 1995
Revision Date: August 23, 1999
Tidel
Engineering, Inc.
EMS-3500
Liquid Discriminatory Probes Part 301-0635, Containment Sump Probes Part
301-0642,
Tidel
Detector #301-0752-001
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type:
|
qualitative
|
Sampling
frequency:
|
continuous
|
Operating
principle:
|
electrical conductivity/hydrocarbon sensitive
polymer (Liquid Discriminatory
Probes Part 301-0635), magnetic switch/float and hydrocarbon sensitive polymer
(Containment Sump Probes Part 301-0642), float switch (Tidel Detector
#301-0752-001)
|
Test
Results:
|
unleaded
gasoline
|
water
|
Liquid
Discriminatory Probes Part 301-0635
|
|
|
Response
time (min)
|
3.59
|
0.96
|
Recovery
time (min)
|
13.18
|
<1
|
Product
activation height (cm)
|
1.76
|
0.49
|
Lower
detection limit (cm)
|
4.19
|
1.52
|
|
|
|
|
|
high*
|
low*
|
Containment
Sump Probes Part 301-0642
|
|
|
|
Response
time (min)
|
6.39
|
4.12
|
4.76
|
Recovery
time (min)
|
>60
|
<1
|
<1
|
Product
activation height (cm)
|
2.27
|
19.22
|
4.31
|
Lower
detection limit (cm)
|
2.32
|
N/A**
|
4.31
|
|
|
|
|
50%
by weight
ethylene glycol in
water
|
30%
by weight
calcium chloride in
water
|
Tidel Detector #301-0752-001
|
high
|
low
|
high
|
low
|
Response
time (min)
|
21.91
|
30.10
|
22.27
|
31.08
|
Recovery
time (min)
|
<1
|
<1
|
<1
|
<1
|
Product
activation height (cm)
|
28.92
|
2.75
|
28.82
|
2.48
|
*The
"high" and "low" refer to high and low level alarm points of
hydrostatic sensors.
**See
Glossary
Specificity
Results (in addition to above for Liquid Discriminatory Probes Part 301-0635 and
Containment Sump Probes Part 301-0642):
Activated:
synthetic gasoline,
diesel, heating oil #2.
Comments:
Liquid Discriminatory Probes Part 301-0635 and Tidel Detector #301-0752-001 are
reusable.
Containment Sump Probes Part 301-0642 was tested to determine its capability of
detecting hydrocarbons floating on water. A
Lower detection limit thickness of 0.04 cm was declared, on average, in 16
minutes, 41 seconds with recovery time averaging 12 minutes, 55 seconds.
Tidel Detector #301-0752-001 is intended to monitor the level of either ethylene
glycol or calcium chloride solutions in interstitial or annular space of a
double-walled tank. Detector
activates an alarm if any significant gain or loss of solution occurs.
Tidel Engineering, Inc.
|
Evaluator:
Carnegie Mellon Research Institute
|
2025 West Beltline Road, #114 |
Tel:
(412) 268-3495
|
Carrollton,
TX 75006
|
Dates of Evaluation: 01/29/93,
02/17/93, 04/20/93
|
Tel:
(800) 678-7577
|
|
|