Issue Date: November 22, 1995
Revision Date: September 22, 2009
Tanknology
Proline Test
Series III, Version 1.0
LINE TIGHTNESS TEST METHOD
Certification |
Leak rate of 0.1
gph with PD = 99.0% and PFA = 0.1%. |
Leak
Threshold |
0.05 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4. |
Specification |
System tests
fiberglass and steel pipelines.
Tests are conducted at 150% operating pressure.
Mechanical line leak detector must be removed from pipeline for duration
of test. |
Pipeline
Capacity |
Maximum of 41
gallons. |
Waiting
Time |
None between
delivery and testing.
Minimum of 1 hour between dispensing and testing. |
Test
Period |
Minimum of 1
hour.
Pipe deflection, vapor pockets, and large temperature differences may
produce inconsistent readings, testing to continue until stable conditions
are present.
Test data are acquired and recorded manually.
Manual calculations are performed by the operator on site. |
Calibration |
Sensors must be
calibrated before each test in accordance with manufacturer's
instructions. |