Issue Date: November 22, 1995
Revision Date: November 6, 1997
Tank
Automation, Inc.
Automated
Precision Tank Testing System (APTT System) R-2
VOLUMETRIC TANK TIGHTNESS TEST
METHOD (OVERFILL)
Certification |
Leak rate of 0.1
gph with PD = 99% and PFA = 1%. |
Leak
Threshold |
0.05 gph.
A tank system should not be declared tight if the test result indicates a
loss or gain that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4. |
Tank
Capacity |
Maximum of 15,000
gallons.
Tank must be minimum 100% full. |
Waiting
Time |
Minimum of 10
hours, 30 minutes between delivery and testing.
Minimum of 2 hours, 30 minutes between "topping off" and
testing.
There must be no dispensing or delivery during waiting time. |
Test
Period |
Minimum of 1
hour.
Test data are acquired and recorded manually for level measurement and by
system's computer for temperature measurement.
Leak rate is calculated from last 1 hour of test period data.
There must be no dispensing or delivery during test. |
Temperature |
Average for
product is determined by a minimum of 10 thermistors. |
Groundwater |
Groundwater
presence must be determined to a depth of 5 feet below grade in tank
excavation backfill.
Product level must be a minimum of 5 feet 6 inches above grade to ensure a
minimum net pressure of 1 psi at bottom of tank during test. |
Calibration |
Thermistors and
level sensors must be checked annually and, if necessary, calibrated in
accordance with manufacturer's instructions. |
Comments |
Not evaluated
using manifolded tank systems. |
Tank
Automation, Inc.
|
Evaluator:
Wildwood Engineering
|
Manufacturer’s Previously Listed Contact Information is No
Longer Valid.
|
Tel:
Unavailable
|
|
Date of
Evaluation: 11/14/90
|
|