Issue Date: November 22, 1995
Revision Date: December 31, 2009

Syscorp, Inc.

Store Vision Version E.2

STATISTICAL INVENTORY RECONCILIATION TEST METHOD (QUALITATIVE)

Certification Leak rate of 0.2 gph with PD = 95.7% and PFA = 0%.
Leak Threshold 0.0834 gph. 
A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold.
Applicability Gasoline, diesel. 
Tank Capacity Maximum of 12,000 gallons.
Data Requirement Minimum of 29 days of product level and flow through data.
Comments Not evaluated using manifolded tank systems. 
Of 120 data sets submitted for evaluation, 32 were inconclusive. 
Median monthly throughput of tanks evaluated was 8,097 gallons. 
Leak rate of 0.2 gph was used in evaluation. Data sets evaluated were supplied by evaluator.

 

Syscorp, Inc.

Evaluator:  Midwest Research Institute

531 Highland Park Circle

Tel:  (816) 753-7600

Birmingham, AL 35242

Date of Evaluation:  09/30/93

Tel:  (205) 981-7413

 

 