Issue Date:  January 11, 2001

Simone Engineering, Inc.

Magnetrol Model 918 Ultrasonic Point Level Switch with ABB Automation Freelance 2000 Control System

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative, non-discriminating

Sampling frequency:

continuous

Operating principle:

electrical conductivity, ultrasonic

Test Results:

 

trichloroethylene

acetone

water

Lower detection limit (in)

0.143

0.166

0.164

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Specificity Results:
Evaluator claims sensors will respond to any liquid after threshold is exceeded.

Comments:
The Magnetrol Model 918 has not been evaluated for application with petroleum hydrocarbons.  The sensor has been evaluated specifically for application in water, acetone, and trichloroethylene.
The ABB Automation Freelance 2000 was used to detect the 8 to 16 milliamp change that occurred in the Magnetrol sensor when it became submerged in product.  Audible and visual alarms were activated when the sensor indicated that alarm conditions were present.

 

FCX Performance

Evaluator:  Ken Wilcox Associates

55 North Lively Blvd.

Tel:  (816) 443-2494

Elk Grove Village, IL 60007

Date of Evaluation:  01/27/00

Tel:  (847) 806-1885

 

E-Mail:  chill@FCxPerformance.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.