Issue Date: November
14, 1997
Revision Date: September 11, 1998
Ronan
Engineering Co.
Ronan
Controller Models X76S; X76VS; X76LVC; TRS76; X76ETM, LVCS; X76CTM-N4;
X76ETM-4X; X76-4X, -3, -6, -9, -12; X76AST-4X with Ronan Sensor Models LS-3
N.C.; LS-3 N.O.; LS-30; LS-7; HVA; LS-3SS; LS-1
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
float
switch |
Test
Results:
|
unleaded
gasoline
|
water
|
LS-3 N.C. (normally closed)
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
2.77
|
2.31
|
LS-3 N.O. (normally open)
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
2.31
|
1.70
|
LS-30 (high level)
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
N/D*
|
15.24
|
LS-30 (low level)
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
N/D
|
4.72
|
LS-7
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
1.09
|
0.81
|
HVA
|
|
|
Detection
time (sec)
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
Lower
detection limit (cm)
|
0.84
|
0.71
|
*See
Glossary
Comments:
Sensors are reusable.
LS-3SS is identical to LS-3 N.C. and LS-3 N.O. except that LS-3SS also tests for
methanol and has a stainless steel float.
The
only difference between LS-1 and LS-3 is that LS-1 is smaller in diameter.
Ronan
Engineering Co.
|
Evaluator:
Ken Wilcox Associates
|
21200
Oxnard St.
|
Tel:
(816) 443-2494
|
Woodland
Hills, CA 91367
|
Date
of Evaluation: 02/06/92
|
Tel:
(800) 327-6626
|
|
|