Issue Date: November 22, 1995
Revision Date: March 10, 2000
Ronan
Engineering Co.
X-76 ETM, X-76
ETM-4X (Magnetostrictive Probe)
AUTOMATIC TANK GAUGING METHOD
Certification |
Leak rate of 0.2
gph with PD = 99.96% and PFA = 0.044%.
Leak rate of 0.1 gph with PD = 95.34% and PFA = 4.66%. |
Leak
Threshold |
0.1 gph for leak
rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A tank system should not be declared tight if the test result indicates a
loss that equals or exceeds this threshold. |
Applicability |
Gasoline, diesel,
aviation fuel, fuel oil #4. |
Tank
Capacity |
Maximum of 15,000
gallons.
Tank must be between 50 and 95% full for leak rates of 0.2 and 0.1
gph.
Tank must have minimum product height of 12 inches or be 14% full,
whichever is higher, when leak threshold is set at 0.049 gph (PD = 95% and
PFA = 5%). |
Waiting
Time |
Minimum of 2
hours between delivery and testing for leak rate of 0.2 gph.
Minimum of 8 hours between delivery and testing for leak rate of 0.1
gph.
There must be no dispensing or delivery during waiting time. |
Test
Period |
Minimum of 4
hours.
Test data are acquired and recorded by system's computer.
Leak rate is calculated from data determined to be statistically
valid.
There must be no dispensing or delivery during test. |
Temperature |
Average for
product is determined by a minimum of 1 resistance temperature detector (RTD). |
Water
Sensor |
Must be used to
detect water ingress.
Minimum detectable water level in the tank is 0.947 inch.
Minimum detectable water level change is 0.0254 inch. |
Calibration |
RTD and probe
must be checked and, if necessary, calibrated in accordance with
manufacturer's instructions. |
Comments |
Not evaluated
using manifolded tank systems. Therefore, this certification is only
applicable when there is a probe used in each tank and the siphon is broken
during testing.
Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to
lower head pressure).
Consistent testing at low levels could allow a leak to remain
undetected.
EPA leak detection regulations require testing of the portion of the tank
system which routinely contains product.
X76ETM-4X console has different housing which allows it to be mounted
outside. |
Ronan
Engineering Co.
|
Evaluator:
Ken Wilcox Associates
|
21200
Oxnard St.
|
Tel:
(816) 443-2494
|
Woodland
Hills, CA 91367
|
Date
of Evaluation: 02/07/91,
11/21/91
|
Tel:
(800) 327-6626
|
|
|