Issue Date: November 4, 2013 Pneumercator Company, Inc.
TMS 1000, TMS 2000W (wireless) with ES825-400F, 400XF Discriminating Liquid Sensors INTERSTITIAL DETECTOR (LIQUID-PHASE) Detector:
Test Results:
Specificity Results: Manufacturer claims sensors will respond to any liquid after sensor’s threshold is exceeded. Manufacturer’s Specifications: All sensors are designed to connect to a controller system that indicates the status of the sensor. Manufacturer indicates that discriminating sensors ES 825-400F and 400XF incorporate an optical liquid sensor and a conductivity sensor. The sensors discriminate between product and water by determining if the optical sensor, which responds to any liquid, or the conductivity sensor, which responds only to water, causes an alarm. Comments: “F”, “XF”, and “CF” are variations of the same sensor distinguished by the material they are made of, such as PVC and Teflon.
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary | Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment. |