Issue Date: November 22, 1995
Revision Date: January 11, 2001

Pneumercator Company, Inc.

LDE 700, LDE 740, LDE 9000 with Sensor Probe Models 9-901, 9-902, 9-903

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

capacitance

Test Results:

 

unleaded gasoline

synthetic gasoline

Detection time (sec)

<1

<1

Fall time

manual reset

manual reset

Lower detection limit (cm)

 

 

    9-901

0.32

0.36

    9-902

0.36

0.34

    9-903

0.76

0.74

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.

Comments:
Sensors are reusable.
Capacitance probes do not work with oxygenated fuels.

 

Pneumercator Company, Inc.

Evaluator:  Ken Wilcox Associates

1785 Expressway Drive North

Tel:  (816) 443-2494

Hauppauge, NY 11788

Date of Evaluation:  12/14/93

Tel: (800) 209-7858, (631) 293-8450x112   

E-mail:  jlevy@pneumercator.com

 
UEL: www.pneumercator.com

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.