Issue Date: April 18, 1997
Revision Date: November 25, 2015

Pneumercator Company, Inc.

LC 1000 Series, E-14-29, E-700-1, LDE-700, LDE-740, TMS 2000, TMS 3000 with
Level Sensor Models LS600AB, RSU800

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float switch

Test Results:

unleaded gasoline

diesel

water

LS600AB

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

3.32

3.28

3.18

RSU800 (low level)

 

 

 

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Lower detection limit (ppm)

2.57

2.53

2.31

RSU800 (high level)

 

 

 

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Lower detection limit (ppm)

13.31

13.24

13.01

Specificity Results:
Manufacturer claims sensors will respond to any chemically-compatible liquid having a viscosity below 1500 cps, provided liquid does not have sticky or gummy properties.

Comments:
Sensors are reusable.

 

Pneumercator Company, Inc.

Evaluator:  Ken Wilcox Associates

1785 Expressway Drive North

Tel:  (816) 443-2494

Hauppauge, NY 11788

Date of Evaluation:  01/22/96, 01/14/10

Tel: (800) 209-7858, (631) 293-8450 x112 (Revised 03/02/01)

E-mail:  jlevy@pneumercator.com

 
UEL: www.pneumercator.com

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.