Issue Date: March 1, 2024
PMP
Corporation
PMP
Tank Interstitial Sensors 63409, 63420, and 63460 as evaluated
with the Veeder-Root TLS-450 Plus
console Series (version 010.J.233.54 software)
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating
principle: |
float switch |
Test
Results:
Fiberglass
Tank Sensor 63409 |
premium gasoline |
diesel* |
water |
E10 |
E25 |
E85 |
Lower
detection limit (in) |
064 |
0.60 |
0.56 |
0.66 |
0.64 |
0.63 |
Precision
(in) |
0.03 |
0.02 |
0.03 |
0.02 |
0.04 |
0.03 |
Detection
time (sec) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
Recovery time (sec) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
|
|
|
|
|
|
|
Steel Tank Sensors 63420, 63460 |
|
|
|
|
|
|
Lower
detection limit (in) |
1.37 |
1.31 |
1.14 |
1.33 |
1.38 |
1.39 |
Precision
(in) |
0.01 |
0.01 |
0.01 |
0.03 |
0.03 |
0.01 |
Detection
time (sec) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
Recovery
time (sec) |
<1 |
<1 |
<1 |
<1 |
<1 |
<1 |
*Evaluations determined
these sensors' responses to the liquids shown above. Biodiesel blends B6-B20
meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an
alarm if the lower detection limit is exceeded. Responses to these fuels were
not determined but would be expected to be very similar to the diesel
responses.
Comments:
63420 & 63460 are identical except
for cable length.
These
sensors were third party evaluated with a Veeder Root TLS-450 Plus console
Series 8600 (version 010.J.233.54 software).
PMP Corporation claims that these sensors will work with these other consoles:
the TLS-450 series, TLS-4 series, TLS-350 series, TLS-300 series, ILS-350,
Simplicity, Gilbarco EMC series, EMC Basic series, EMC-PC, Red Jacket ProMax
and ProPlus.
PMP Corporation |
Evaluator: Solutions
Engineering Group |
25 Security Drive |
420 N. Main Street |
Avon, CT 06001-0422 |
Montgomery, IL 60538-1367 |
Tel: (860) 677-9656 |
Tel: (630)
701-7703 |
Toll Free: (800)
243-6628 |
Date of
Evaluations: 1/26/2024 |
E-mail: sales@pmp-corp.com |
|
URL: www.pmp-corp.com |
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |
Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations. For full details, please refer to our expanded "DISCLAIMER"
page.