Issue Date: March 1, 2024

PMP Corporation

PMP Dual-point Hydrostatic Sensor 63303 and Mini-Hydrostatic Sensor 63304 as evaluated

with the Veeder-Root TLS-450 Plus console Series 8600 (version 010.J.233.54 software)


INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

 

Output Type:

qualitative

Sampling Frequency:

continuous

Operating principle:

float switch

 

Test Results:

propylene glycol (in water)

 ethylene glycol (in water)

 calcium chloride (CaCl) (in water)

 

water

Dual-Point Hydrostatic Sensor

63303

 

 

Detection time (sec)

<1

<1

<1

<1

Fall time (sec)

<1

<1

<1

<1

Precision (in)

 

 

 

 

Detection Threshold

Low level (in)

1.39

1.43

1.19

1.45

High level (in)

14.18

14.08

13.86

14.12

Mini-Hydrostatic Sensor 63304

Detection time (min)

<1

<1

<1

<1

Fall time (min)

<1

<1

<1

<1

Precision (in)

 

 

 

 

Detection Threshold Level

Low level (in)

1.10

1.04

1.03

1.21

Comments:

63303 is a tall dual-point sensor that indicates both low-level and high-level conditions.

63304 is a shorter, stainless steel body sensor that only registers low-level liquid conditions.

These sensors were third party evaluated with a Veeder Root TLS-450 Plus console Series 8600 (version 010.J.233.54 software).


PMP Corporation claims that these sensors will work with these other consoles: the TLS-450 series, TLS-4 series, TLS-350 series, TLS-300 series, ILS-350, Simplicity, Gilbarco EMC series, EMC Basic series, EMC-PC, Red Jacket ProMax and ProPlus.          

 

PMP Corporation

Evaluator: Solutions Engineering Group

25 Security Drive

420 N. Main Street

Avon, CT 06001-0422

Montgomery, IL 60538-1367

Tel: (860) 677-9656

Tel: (630) 701-7703

Toll Free: (800) 243-6628

Date of Evaluations:  1/26/2024

E-mail: sales@pmp-corp.com

URL: www.pmp-corp.com

 


 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.