Issue Date: November 22, 1995
Revision Date: March 10, 2000
PermAlert
PAL-AT
Models AT20C, AT50C, AT40K
with AGW Sensor Cable, TFH Hydrocarbon Sensor Cable
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Output
type
|
qualitative
|
Sampling
frequency
|
continuous
|
Operating
principle
|
impedance change
|
Test Results:
|
unleaded
gasoline
|
AGW
Sensor Cable
|
1/3
MER*
1348 ft
|
2/3
MER
2644 ft
|
MER
3982 ft
|
Response
time (min)
|
9.92
|
6.25
|
21.28
|
Recovery
time (min)
|
1.0
|
1.0
|
1.0
|
Product
activation height (cm)
|
2.03
|
1.13
|
5.00
|
Detection
length (cm)
|
116.3
|
64.8
|
286.1
|
Lower
detection limits (cm)
|
|
|
|
Product activation
height
|
N/D*
|
N/D
|
5.1
|
Detection
length
|
N/D
|
N/D
|
295.6
|
TFH Hydrocarbon Sensor Cable
|
1368 ft
|
2685 ft
|
4046 ft
|
Response
time (min)
|
3.40
|
7.48
|
16.21
|
Product
activation height (cm)
|
0.65
|
1.33
|
3.53
|
Detection
length (cm)
|
27.7
|
56.8
|
150.4
|
Lower
detection limits (cm)
|
|
|
|
Product activation
height
|
N/D
|
N/D
|
3.
|
Detection
length
|
N/D
|
N/D
|
152.9
|
*
See glossary.
Specificity
Results (in addition to above):
Activated:
synthetic gasoline, diesel, heating oil #2, water (AGW Sensor Cable
only).
Comments:
System
can monitor interstitial spaces.
Evaluations
also covered quantitative leak location.
AGW
Sensor Cable is reusable.
TFH
Hydrocarbon Sensor Cable is not reusable.
Lower
detection limit is calculated at MER only.
Cable is assumed to be equally or more sensitive at shorter lengths.
PermAlert
|
Evaluator:
Carnegie Mellon Research Institute
|
6410 W. Howard St..
|
Tel: (412) 268-3495
|
Niles, IL 60714
|
Date of Evaluation:
01/17/92,
02/11/92
|
Tel: (847) 966-2235
|
|
Email: marketing@permalert.com |
|
URL: www.permalert.com |
|
|