Issue Date: November 22, 1995
Revision Date: April 18, 1997

PermAlert

PAL-AT Models AT20C, AT50C, AT40K
with PHL Hydrocarbon Senso

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity

 

Test Results:

 

 

unleaded gasoline

Response time (min)

1.13

Recovery time (min)

8.83

Product activation height (cm)

0.53

Lower detection limit (cm)

0.38

Specificity Results (in addition to above):
Activated:  synthetic gasoline, diesel, heating oil #2.
Not activated: water.

Comments:
Sensors are reusable.

 

PermAlert

Evaluator:  Carnegie Mellon Research Institute

6410 W. Howard St.

Tel:  (412) 268-3495

Niles, IL 60714

Date of Evaluation:  02/05/92

Tel:  (847) 966-2235

 

Email: marketing@permalert.com
URL: www.permalert.com
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.