Issue
Date: November 7,
2001
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)
SiteSentinel
Controller with Single Float Switches
Part #30-3221-1, Part #30-3221-1A,
Part #30-3221-1B
Brine Reservoir Sensor and Dual Float Sensor Part #30-3221-2
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)
Detector:
Output
type: |
qualitative |
Sampling
frequency: |
continuous |
Operating principle: |
float
switch |
|
unleaded
gasoline
|
diesel
|
water
|
Part #30-3221-1
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
Lower
detection limit (in)
|
1.225
|
1.171
|
1.123
|
Part #30-3221-1A
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
Lower
detection limit (in)
|
1.513
|
1.487
|
1.375
|
Part #30-3221-1B
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
Lower
detection limit (in)
|
0.876
|
0.828
|
0.562
|
Part #30-3221-2 (Brine Reservoir Sensor)
|
|
|
|
Detection
time (sec)
|
-
|
-
|
<1
|
Fall
time (sec)
|
-
|
-
|
<1
|
Low
level alarm - Lower detection limit (in)
|
-
|
-
|
2.495
|
High
level alarm - Lower detection limit (in)
|
-
|
-
|
10.389
|
Part #30-3221-2 (Dual Float Sensor)
|
|
|
|
Detection
time (sec)
|
-
|
-
|
<1
|
Fall
time (sec)
|
-
|
-
|
<1
|
Low
level alarm - Lower detection limit (in)
|
-
|
-
|
2.533
|
High
level alarm - Lower detection limit (in)
|
-
|
-
|
10.492
|
Specificity
Results:
Evaluator indicates that single
float sensors work with any liquid.
Comments:
Evaluator
indicates that Sensor Part #30-3221-2 can operate either as a brine reservoir
sensor or a dual float sensor based on orientation of the lower float.
OPW Fuel Management Systems
|
Evaluator:
Ken Wilcox Associates
|
6900 Santa Fe Dr.
|
Tel: (816) 443-2494
|
Hodgkins, IL 60525-9909
|
Date of Evaluation:
08/03/00
|
Tel: (708) 485-4200
|
|
E-Mail:
info@opwfms.com |
|
URL: www.opwfms.com |
|
|